Continuous electronic climate controller, KTRVB Surface-mounted installation – Design Berlin 2000

Technical data

Application

Design:

Berlin 2000

Room temperature controller for continuous control of valve actuators. Controller for 2-pipe systems (1-duct), 4-pipe systems (2-duct) and mixing chambers.

Surface finish: Housing colour: Housing material:

matt

pure white, like RAL 9010

ABS plastic −20 … +70 °C

Storage temperature: Operating voltage: Permissible atmospheric humidity: Electrical connection: Mounting/attachment:

24 VDC, 24 VAC, 50 Hz

max. 95% rel. humidity, non-con- densing

screw-type terminals Surface-/wall-mounting

Protection rating: Protection class: Safety and EMC: Switching element: General features:

IP 30

III

according to DIN EN 60730

electronic with analogue output signal climate controller for individual room control with proportionally controlled valve; mechanical range restriction; external setting

Type/image

Item no.

Features

Circuit diagram PG

KTRVB-048.100

General features: scale: degrees Celsius Ambient temperature: 0 … 50 °C

DA450000

I

Output signal: consistently 0…10 V or 10…0 V (can be switched using a jumper), max. 5 mA Sensor: NTC internal Control function: Heating or cooling with adjustable p-band, aligned to 5 V at setpoint temperature Control range: 5 … 30 °C Hysteresis: 0 K, since control is always via the p-band in the

range from +0.5 K … 3 K (adjustable) Pipe system compatibility: 2-pipe

KTRVB-048.200

General features: Relative scale Ambient temperature: 0 … 50 °C Output signal: consistently 0… 10 V or +10… 0 V (can be switched using a jumper), max. 5 mA Sensor: NTC, internal Control function: Heating or cooling with adjustable p-band, aligned to 5 V at setpoint temperature Control range: 13 … 29 °C Setting range: −3 … +3 K (the pre-set “zero point” of approx. 21 °C can be adjusted in the machine by +/− 5 K) Hysteresis: 0 K, since control is always via the p-band in the

DA450100

I

range from +0.5 … 3 K (adjustable) Pipe system compatibility: 2-pipe

KTRVB

Catalogue 2022 | Page 133