PRODUCT CATALOGUE 2022 | alre.de

Plant room double thermostat RTKSA Capillary system – external sensors – 2 separate setting ranges

Technical data

Application

Colour:

Anthracite grey (similar to RAL 7016), front side transparent

RTKSA plant room thermostats were specially developed for use in industrial halls, exhibition halls, air halls and greenhouses. When used as a frost protection controller, the higher tolerances at the end of the scale must be observed.

Sensor material: V4A Max. sensor temperature Top scale value +15% Max. head temperature: 50 °C Permissible atmospheric humidity:

Max. 95% rel. humidity, non-condensing

Operating voltage:

none

2 separate setting ranges, heat- ing and/or cooling.

Max. switching current:

NC contact: 16 (2.5) A at 230 VAC +10% 0.25 A at 230 VDC +10% NO contact: 6.3 (2.5) A at 230 VAC +10% 0.25 A at 230 VDC +10% Min. 100 mA at 24 V (AC/DC) 230 VAC 50/60 Hz, 230 VDC

Type testing by TÜV in accor- dance with DIN EN 14597

Min. switching current: Max. switching voltage: Min. switching voltage:

24 VAC/50 Hz, 24 VDC

Switching element: Switching contact: Control function:

microswitch

2 x togglers, potential-free

Heating or cooling, heating and cooling

Hysteresis:

1.3 K

Electrical connection: Mounting/attachment:

Push-in terminals

wall mounting

Protection class: Protection rating: Safety and EMC:

I

IP 54 (optionally IP 65)

In accordance with DIN EN 60730 (VDE 0631)

Sensor:

liquid-filled capillary Scale: degrees Celsius

General features:

Type

Item no.

1st Control range

2nd Control range Features

PG

RTKSA-114.110 RTKSA-114.010

KA011100

0 … +50 °C (TW, internal)

0 … +50 °C (TW, internal) −10…+40 °C (TW, internal)

2 x internal setting 2 x internal setting

II II

KA011101 −10…+40 °C (TW, internal)

TW = temperature monitor

Accessories

Item no.

Features

PG

JZ-33

KA999904 Seal Set for RTKSA (for doublethermostats, 2 pieces neccassary), Protection rating: IP 54

II

Type comparison (old/new type)

Old alre types Control range

Hystere- sis

New alre types Control range

Hystere- sis

JET-30

10…45 °C (external) TR 0 ... 35 °C (internal) TW 10…+45 °C (internal) TW 0…+35 °C (internal) TW

approx. 1 K

RTKSA-114.110

0…+50 °C (internal) TW 0…+50 °C (internal) TW

1.3 K

JET-31

approx. 1 K

TR = temperature controller, TW = temperature monitor

Scan the QR code now and watch the "New thermostats in plant engineering" product film. More in- formation at a glance.

RTKSA

RTKSA (2x)

106 170

heating cooling

57,5

4

2

1

 Catalogue 2022 | Page 158