Duct thermostat JTU-1 … -50 Capillary system – TÜV-tested

Technical data

Application

Housing colour: Sensor material:

grey

Minimum or maximum thermostat for inflow air monitoring and fan regula- tion in ventilation and air conditioning systems. Overheating protection thermostat for electrical heat registers and directly fired air heaters with oil and gas operation. Attention: Assemble the device in a vibration-free manner in order to avoid malfunctions and/or sensor rupture. JTU-20, -3: Type testing by TÜV in accordance with DIN EN 14597, for hot air heaters in accordance with DIN 4794

Cu

Ambient temperature: Permissible atmospheric humidity: Max. sensor temperature

–15 … +80 °C

Max. 95% rel. humidity, non-con- densing

200 °C

Operating voltage:

none

Max. switching current: Min. switching current: Max. switching voltage: Min. switching voltage: Switching element: Switching contact: Electrical connection: Mounting/attachment:

15 (8) A 150 mA

230 VAC, 50 Hz 24 VAC, 50 Hz

microswitch

toggler, potential-free screw-type terminals mounting on air duct

Protection rating: Protection class: Safety and EMC:

IP 40

I

according to DIN EN 60730

Sensor:

liquid-filled capillary, active over its entire length internal setting, scale: degrees Celsius

General features:

Type

Item no.

Control range

Hysteresis (approx.)

Capillary length

Features

PG

JTU-50

E6100000 –25…+65 °C 1.5 K

350 mm Control function: heating or cooling, TW 350 mm Control function: heating or cooling, TW, intrinsic safety, protection against cold 350 mm Control function: heating or cooling, locked when the temperature is rising, STB, intrinsic safety, protection against cold, overheating protection 1250 mm Control function: heating or cooling, locked when the temperature is rising, STB, intrinsic safety, protection against cold 350 mm Control function: heating or cooling, TW 350 mm Control function: heating or cooling, locked when the temperature is rising, TB

II

JTU-1

E6100012

20 … 100 °C 8 … 30 K adjustable

II

JTU-3

E6100036

20…100 °C external reset

II

JTU-20

E6100075

20…100 °C external reset

II

JTU-5

E6100048

60 … 140 °C 8 … 30 K adjustable

II

JTU-6

E6100051

60…140 °C external reset

II

TW = temperature monitor, STB = safety temperature limiter, TB = temperature limiter JTU-2 is replaced by JTU-3. Intrinsic safety / protection against cold: The devices are intrinsically safe, i.e., upon loss of the sensor medium owing to sensor rupture, for example, the burner is switched off. Since minus temperatures generate the same effect through volume reduction of the sensor medium, the devices are adjusted by means of the “cold screw” such that they switch off the burner only at temperatures below −15 °C. They can only be switched on again manually at temperatures above approx. –5 °C by means of the manual reset button. Overheating protection : This device provides protection from uncontrolled overheating, which is caused, for example, by a heat build-up or by creeping capillary filling losses when there is invisible damage to the sensor or the capillary tube etc. Upon reaching a temperature of 220 °C, the safety slot in the sensor melts and, in reaction to losing the filling medium, the device switches off the burner towards the safe side. The burner cannot be switched on