PRODUCT CATALOGUE 2022 | alre.de

Differential pressure switches JDW-3 to 10 / JDL-111 … 116

Technical data

Application

Housing colour:

black

Monitoring of overpressure, differ- ential or under-pressure of air and incombustible, non-aggressive gases. Exhaust or fan monitoring or flow monitor for securing electrical heat registers, as filter monitoring, air pressure shortage safeguard, limit value controller. JDW- …: Supplied without mounting bracket; can be screwed on directly (with 2 screws).

Ambient temperature: Permissible atmospher- ic humidity: Max. sensor tempera- ture Permissible medium temperature:

–15 … +80 °C

Max. 95% rel. humidity, non-condensing

80 °C

JDW-3

–15 … +80 °C

Operating voltage:

none

Min. switching current: 1 mA Max. switching voltage: 230 VAC/50 Hz, 24 VDC Min. switching voltage: 12 VAC/50 Hz, 12 VDC Switching element: microswitch Switching contact:

JDW-...Z: Supplied with attached mounting bracket JZ-10.

JDL-111

toggler, gold contact, potential-free switches if the pressure is undershot or exceeded

JDL …: Supplied with attached mounting bracket JZ-10.

Control function:

Pressure connection: Mounting/attachment: Electrical connection:

6.2 mm

Note: Once the differential pressure switch has connected a voltage > 24 V and a current > 0.1 A,the gold layer at the contacts will have burnt away. Thereafter, the differential pressure switch can only be operated at this or a higher power. Note: The hose set is not a part of the delivery scope and must be ordered separately.

wall mounting

screw-type terminals

Protection class: Protection rating: Safety and EMC:

II

JDL-112

IP 54

according to DIN EN 60730

Sensor:

pressure membrane

Function type:

monitor (JDL-116 A controller)

Conversion table pressure

Pa

kPa

bar

mbar

mmWs 0.101971 101.971 10197.1 10.1971

1 Pa

= = =

1

0.001

0.00001

0.01

1 kPa 1 bar

1,000

1

0.01

10

100,000

100 0.1

1

1,000

1 mbar = 1 mmWs =

100

0.001

1

9.80665

0.00980665

0.0000980665

0.0980665

1

Type

Item no.

Control range

Max. pressure

Hysteresis (dependent on setting range)

Features

PG

JDW-3

H531002

20 … 330 Pa

5,000 Pa approx. 8 … 20 Pa Max. switching current: 1.5 (0.4) AAC, 1 (0.2) ADC Internal setting 5,000 Pa approx. 8 … 20 Pa Max. switching current: 1.5 (0.4) AAC, 1 (0.2) ADC internal setting, fixing bracket 5,000 Pa approx. 10 … 25 Pa Max. switching current: 1.5 (0.4) AAC, 1 (0.2) ADC Internal setting 5,000 Pa approx. 10…25 Pa Max. switching current: 1.5 (0.4) AAC, 1 (0.2) ADC internal setting, fixing bracket

II

JDW-3 Z

H531001

20 … 330 Pa

II

JDW-5

H530996

30 … 500 Pa

II

JDW-5 Z

H531000

30 … 500 Pa

II

JDW-10

H530997

400…1600 Pa 5,000 Pa approx. 30…60 Pa Max. switching current: 1.5 (0.4) AAC, 1 (0.2) ADC Internal setting II

JDL-111

H5309098

20 … 300 Pa

15,000 Pa approx. 10…15 Pa Max. switching current: 5 (1) AAC, 1 (0.2) ADC internal setting, silicon-free 30,000 Pa approx. 22…33 Pa Max. switching current: 5 (1) AAC, 1 (0.2) ADC internal setting, silicon-free

II

JDL-112

H5309100

40 … 600 Pa

II

JDL-115

H5309136

100…1,000 Pa 30,000 Pa approx. 20…40 Pa Max. switching current: 5 (1) AAC, 1 (0.2) ADC internal setting, silicon-free 250…5,000 Pa 30,000 Pa approx. 60…150 Pa Max. switching current: 5 (1) AAC, 1 (0.2) ADC internal setting, silicon-free 250…5,000 Pa 30,000 Pa approx. 60…150 Pa Max. switching current: 5 (1) AAC, 1 (0.2) ADC external setting, silicon-free

II

JDL-116

H530960

II

JDL-116 A

H530978

II

Catalogue 2022 | Page 192

Made with FlippingBook Digital Publishing Software