Industrial assembly-type duct sensor IKF1 (Form B) with passive output

Technical data

Application

Housing colour: Housing material:

silver-grey aluminium

The industrial assembly-type duct sensor IKF1 is used for measuring temperatures of liquids and gases in pipes, air ducts or tanks in the mechanical and plant engineering sector. A mounting flange (MF) is required for use in air ducts. If used in liquids, immersion sleeves made of brass with nickel plating (THMs) should be used. For aggressive media, immersion sleeves made of stainless steel V4A (THV) are recommended. Immersion sleeves or mounting flanges are not part of the delivery scope and must be ordered separately as accessories. Sensor wire extendable: Depending on the cross-section of the conductor and the sensor unit type

Sensor tube material: Ambient temperature: Permissible atmospheric humidity: Max. sensor temperature Electrical connection:

V2A (1.4301) −30 … +100 °C

max. 95% rel. humidity, non-condensing

150 °C

screw-type terminals 0.14 mm² up to 2.5 mm² only to safety extra low voltage max. 30 VAC/42 VDC

Tolerances:

PT1000

DIN EN 60751 B

Mounting/attachment:

in immersion sleeves (THMs, THV) for fluids or with mounting flange (MF) in air ducts

Protection rating: Protection class: Safety and EMC:

IP 43

III

according to DIN EN 60730

Sensor characteristic curves:

the sensor characteristic curves can be found in the “Miscellaneous” section From the fitting length (EL), subtract 15 mm to determine the nominal length (NL) of the immersion sleeve, for example, EL = 65 mm corresponds to THV/50 mounting flange for installation in air ducts: MF matching immersion sleeves in brass: Immersion sleeves with brass plating can be found in the “Miscellaneous” section matching immersion sleeves stainless steel (V4A): immersion sleeves made of stainless steel can be found in the “Miscellaneous” section

Immersion sleeves:

Accessories:

Please follow the EMC directives, avoid parallel routing with mains voltage-bearing wires, or use shielded wires.

Sensor

Fitting length (EL) 65 mm (for 50 mm immersion sleeves)

Fitting length (EL) 115 mm (for 100 mm immersion sleeves)

Fitting length (EL) 165 mm (for 150 mm immersion sleeves)

PG

PT 1000

IKF1P 1000 / 50 Item no.: G9150020

IKF1P 1000 / 100 Item no.: G9150150

IKF1P 1000 / 150 Item no.: G9150280

III

Accessories

Item no.

Features

PG

MF

G9990160

mounting flange for integrated duct sensor

III

Dimension schematic, mounting flange MF

Dimension schematic, industrial assembly-type duct sensor

Connection diagram IKF