PRODUCT CATALOGUE 2022 | alre.de

BACnet room controller KTRBUu Flush-mounted installation – Design Berlin UP

Technical data

Application

Design:

Berlin UP (flush-mounted) PC, PMMA, ABS plastic

The alre BACnet individual room controller with graphic display was specially developed for time-dependent heating and cooling operation in 2- or 4-pipe systems. The controller can be used in a wide range of applications, such as hotels, residential, office and business premises as well as hospitals and schools. The communication takes place via BACnet according to DIN EN ISO 16484-5 with the BACnet MS/TP network protocol. The room controller is therefore compatible with all com- mon building automation systems. The control- ler corresponds to the BACnet profile “B-AAC” (BACnet Advanced Application Controller). The predefined applications cover a wide range of applications for room temperature control in room automation. Special colours are available for projects as well as the colors anthracite and aluminum on request.

Housing material: Operating voltage: Ambient temperature: Storage temperature: Permissible atmospheric humidity: Electrical connection:

230 VAC, 50 Hz

0 … 40 °C

−20 … +70 °C

Max. 95% rel. humidity, non-condensing pluggable screw terminals Mains voltage side 0.75 - 2.5 mm² Low voltage side 0.08 - 1.5 mm² In flush-mounted socket, can be adapted to fit virtually any switch range (deep flush-mounted socket recom- mended) see adaptation list on page 55

Mounting/attachment:

Protection rating: Protection class: Safety and EMC:

IP 30

II

according to DIN EN 60730

Max. switching voltage: Min. switching voltage:

230 VAC, 50 Hz 230 VAC, 50 Hz

Switching power: 690 W Max. power consumption: approx. 1 W (2.2 VA) Max. switching current: all 3 (0.5) A (max. 5 valve actuators per output) Switching element: 2 relays Switching contact: 2 NO contacts Output signal:

Switching heating, cooling, heating/cooling, analogue 0…10 V (5 mA) to control a speed-controlled fan Internal NTC, optional exter- nal “Sensor 2” * (NTC 47k), dew point sensor

Sensor:

Control range: Setting range:

5 … 40 °C

Standard setting range for heating (5 … 30 °C), second setting range for cooling (18 … 40 °C)

Hysteresis: Display type:

< 1 K

illuminated graphical display

Pipe system compatibility: 2-pipe and 4-pipe

Type/image

Item no.

Features

Circuit diagram

PG

KTRBUu217.456#21

Surface finish: Glossy Housing colour: pure white, similar to RAL 9010 Scope of delivery: controller, cover 50 x 50 mm, pure white (similar to RAL 9010), glossy, alre frame “Berlin”

UA230000

IV

L N

230V~ 50Hz

SELV

max. 5mA

O3

N

0—10V

D− D+ I1

L

RS485

O2 O1

NTC TPS

3(0,5)A

* Depending on the selected system scheme, a menu setting can be used to select whether control should be based on the internal or external sensor. In the intermediate positions, if both sensors are used, a weighting is applied to the internal room sensor and the external temperature sensor. The weight- ing allows for compensation of different structural conditions such as large window areas or cardinal directions. For very slow controlled systems, it is recommended to assign a higher weighting to the temperature sensor than to the internal room sensor.

Catalogue 2022 | Page 51

Made with FlippingBook Digital Publishing Software