Mechanical room temperature controller, FTR Flush-mounted installation – Design Berlin UP
Technical data
Application
Design:
Berlin UP (flush-mounted)
Control or monitoring of temperatures in closed, dry spaces. Suitable for all heating systems. Valve actuator: normally closed. If normally open heating valves are available, they should be connect- ed to the cooling output of the changeover switch (toggler), e.g., FTR 101.010 Up to a maximum of 10 actuators for valves can be connected (normally closed, NC); up to 5 units on the toggler with a NO contact. The basic controllers in combination with a 55 x 55 mm cover set fit visual- ly perfectly in many switch ranges without the use of an insert frame. The basic controllers in combination with a 50 x 50 mm cover set fit in nearly all switch ranges with the use of an insert frame. More complete solutions (types #21) with alre-frame “Berlin“ (neutral) and cover 50 x50 mm (pure white similar to RAL 9010, glossy) on request.
Housing material:
PA6 plastic 0 … 30 °C
Ambient temperature: Storage temperature: Permissible atmospheric humidity: Electrical connection:
−20 … +70 °C
Max. 95% rel. humidity, non-con- densing Spring-loaded terminals (lever actu- ation type) in flush-mounted socket – with cover set 50 x 50 mm or 55 x 55 mm, can be used with almost all switch ranges (deep flush-mounted socket recom- mended)
Mounting/attachment:
Protection rating: Protection class:
IP 30
II, if properly mounted, with 24 VAC, protection class III according to DIN EN 60730
Safety and EMC:
Max. power consumption:
< 0.5 W
Switching element:
bimetallic contact
Output signal:
switching
Sensor:
bimetal
Control range: Setting range:
5 … 30 °C 5 … 30 °C
Hysteresis:
approx. 0.5 K at a temperature change of max. 4 K/h
General features:
thermal feedback; multi-digit display * … 6
Type/image
Item no.
Features
Circuit diagram
PG
FTR 101.000#00
General features: Mechanical range limitation; external setting; protective cap; Contact protection cover; VDE tested
UA010017
I
Operating voltage: 230 VAC, 50 Hz Max. switching current: 10 (4) A
Max. switching voltage: 230 VAC, 50 Hz Min. switching voltage: 230 VAC, 50 Hz Switching power: 2300 W Switching contact: NC contact (max. 10 actuators) Control function: Heating
Cover sets are offered in various designs (see the separate over- view, “alre flush-mounted range (cover sets)”)
and are not included in the delivery. Suitable set no: JZ-001.xxx, e.g.:
cover set 50 x 50 mm, pure white, glossy: JZ-001.000 cover set 55 x 55 mm, pure white, glossy: JZ-001.100 BUSCH-JAEGER cover set Reflex SI/SI Linear, pure white, glossy: JZ-001.200 / BJ Future linear, solo, axcent, carat, studio white (RAL 9016), glossy; JZ-001.320 / BJ like FTR 101.000#00 but scope of delivery as follows: Controller, alre frame “Berlin” (neutral), cover 50 x 50 mm, pure white (like RAL 9010), glossy
FTR 101.000#21
UN010009
I
Catalogue 2022 | Page 76
Made with FlippingBook Digital Publishing Software