WWW.CONTROLTECHNIQUES.COM
4 x Digital inputs (1 frequency or thermistor input) 1 x Digital input / output (can be used as a frequency or PWM output to represent analogue value)
Digital
Digital Input Logic
Positive
Relay
1 x Relay (single pole, single throw)
Accuracy
Frequency 0.02 %,Analogue input 1: 11 bit plus sign,Analogue input 2: 11 bit. Current typical 2 %.
3 x Analogue inputs (default) / Digital inputs 4 x Digital input / output 1 x Digital input 2 x Relays (single pole, single throw) Positive or Negative Logic (PNP or NPN)
Extra I/O with SI-I/O Option Module (Available as an Accessory)
Mounting & Environment Supported Encoders with SI-Encoder (Available as an Accessory)
Incremental AB (5 V, 8 V, or 15 V)
IP20 Conduit Box UL Type 1 ingress protection (available as an accessory)
IP Rating
Storage Temperature
-40 °C to 60 °C (-40 °F to 140 °F) -20 °C to 40 °C (-4 °F to 104 °F)
Operating Temperature without De-Rate
-20 °C to 60 °C (-4 °F to 140 °F) Frames 1 to 4 -20 °C to 55 °C (-4 °F to 131 °F) Frames 5 to 9
Operating Temperature with De-Rate
Cooling Altitude Humidity Pollution
Integral cooling fan
≤3000 m (≤1000 m no de-rate; 1000 m to 3000 m derate 1 % every 100 m)
95 % non-condensing at 40 °C / 104 °F - EN61800-2(3k3) Pollution degree 2 - dry, non-conducting pollution only
Reference standard IEC60068-2-27, IEC60068-2-29 bump test, IEC60068-2-64 random vibration test, IEC60068-2-6, EN61800-5-1 sinusoidal vibration test. Tested to Environmental Category ENV3
Vibration
Mechanical Shock
Tested in accordance with IEC 60068-2-27 and IEC 60068-2-29
Frame 1 to 4 – Surface mount via mounting holes or DIN Rail mount Frame 5 to 9 – Surface mount via mounting brackets or through-panel mount via through-panel mounting kit
Mounting Methods
Mounting Clearance Overvoltage Category Corrosive Environments
0 mm either side, 100 mm above and below
Category III
EN 60721-3-3 ISO9223 Class C3
Maximum Motor Cable Length
75 m Frame 1 | 100 m Frames 2 to 4 | 200 m Frames 5 to 6 | 250 m Frames 7 to 9
Standards Approvals
CE (European Union), cUL Listed (USA and Canada), DNV (marine applications), KC (Korea), RCM (Australia/ New Zealand), EAC (Russian Customs Union), UKCA (United Kingdom), C-Tick (Australia)
E171230
UL 508C IEC/EN/KN 61800-5-1 CSA C22.2 No.274 GB12668.501-2013
Product Safety Standards
C300 models only: The Safe Torque Off (STO) function may be used as a safety component of a machine. Type examination certificates by TÜV Rheinland:
Frame sizes 1 - 4: No. 01/205/5383.03/18 Frame sizes 5 - 9: No. 01/205/5387.02/18 Functional safety parameters: EN ISO 13849-1 - Cat 4, PLe EN61800-5-2/EN62061/IEC 61508 - SIL 3 UL functional safety approval: FSPC E171230
TÜV
IEC/ EN 61800-3 Immunity and Emissions (Meets equipment category C3 with internal filter,with an external EMC filter C1 or C2 can be achieved) EN 61000-6-2: Immunity for industrial environments (Complies)
Product EMC Standards
EN 61000-6-4: Emissions for industrial environments (External EMC filter required to comply) EN 61000-3-2: Harmonic current emissions (External line reactor required to comply)
RoHS
Complies with the Restriction of Hazardous Substances Directive (2011/65/EU)
Immunity Compliance
Second environment (Industrial)
ISO
Manufacturing facilities comply with ISO 9001:2015 and ISO 14001
Warranty Warranty
5Years (warranty terms and conditions apply)
Accessories Remote Interfaces Filters & Cables
Remote keypad IP66, Remote keypad RTC, HMI
External EMC filters, line reactors
PC Tools Programming Cable
CT communications cable
AI-485 24 V Adaptor (MODBUS), SI-EtherCAT, SI-PROFIBUS, SI-Ethernet , SI-DeviceNET, SI-CANopen, SI-PROFINET , SI-POWERLINK, SI-Encoder, SI-I/O, SI-BACnet IP, SI-Interbus (500 kBd or 2 MBd)
Communication & Feedback, SI-Options
Back-up & Cloning
AI-Back-up Adaptor & AI-Smart Adaptor (Includes 4GB SD card)
Conduit Box
For UL Type 1 ingress protection
15