Remtron Component Solutions.xlsx

Schneider Electric Soft Starters

Soft Starter References

Altisart 01 Soft starter for simple machines For 1‐ph and 3‐ph motors up to 15kW Reduced voltage starting, built‐in bypass relay.

Soft start only, 1‐phase/3‐phase supply voltage: 110‐480V 50/60Hz > Controls 1 phase to limit the motor torque, soft start only > Rated at 20 starts/hr with a maximum start time of 5 sec or equivalent cycle (class 10)

> For 1‐ph connection, connect the GV2 breaker poles in series > For 3‐ph connection, a line contactor is required to stop the motor > Requires an external control voltage (24Vdc or 230Vac)

400V

230V

Associated Motor C/B

In (A)

3‐ph kW 1‐ph kW D(mm) W(mm) H(mm)

Part Number

SEATS01N103FT SEATS01N106FT SEATS01N109FT SEATS01N112FT SEATS01N125FT

SEGV2P08 SEGV2P10 SEGV2P14 SEGV2P16 SEGV2P22

3 6 9

1.1 2.2

0.37 0.75

100

100

22.6

4

1.1 1.5 2.2

130

124

45

12 25

5.5

11

Soft start/soft stop, 3‐phase supply voltage: 380‐415V 50/60Hz > Controls 2 phases to limit the motor torque, soft start and soft stop > 6A to 22A starters are rated for a max of 10 starts/hr, with a max start time of 10 sec or equivalent cycle (class 10). The 32A (15kW) starter is rated for 5 starts per hour. > For applications requiring controlled start and stop, divide the max possible number of starts/hr by 2 > Control voltage supply built in to starter Associated 400V Part Number Motor In (A)

SEATS01N103FT

3‐ph kW D(mm) W(mm) H(mm)

SEATS01N206QN SEATS01N209QN SEATS01N212QN SEATS01N222QN

SEGV2P10 SEGV2P14 SEGV2P16 SEGV2P22

6 9

2.2

130

45

124

4

12 22 32

5.5

11

130

45

154

SEATS01N232QN 15 SEATS01N206QN _________________________________________ www.remtron.com.au Page 3 of 129 shop.remtron.com.au SEGV2P32

Made with FlippingBook Learn more on our blog