3. TYPICAL DRAWING OF AMTECH STREAMER AMBIENT TOWER

4. INSPECTION 4.1 Upon receipt of the Amtech Streamer Ambient Tower, all components must be checked for damage or potential loss incurred during shipping. Damage must be noted on the bill of lading and a claim filed with the carrier immediately. Clean Air Industries should be notified immediately upon receipt of the unit, regarding any missing or lost components. 5. THEORY OF OPERATION 5.1 The Amtech Streamer Ambient Tower features a plug and play setup for general dust collection ambient applications. During normal operation, air flows into the collector through the louvered inlet, or the optional Spark Eliminator plenum. Once into the filter cabinet, the air is filtered through the cartridge filter, allowing clean air to pass through the blower and out through the multi-directional outlet of the Amtech Streamer Ambient Tower. A portion of the dust will collect on the surface of the cartridge media as the air passes through the filter, and into the blower. The dust that collects on the cartridge media will periodically be dislodged by the reverse jet pulse cleaning system. This system is electronically controlled and is usually configured to monitor the differential pressure across the filter media. When the differential pressure reaches the adjustable set point, a brief burst of compressed air will be released into the core of the cartridge filter to dislodge the dust from the filter surface. The dislodged dust gradually migrates towards the settling chamber, which can either be a drum system or dust tray system.