7.2 Mechanical NOTE: All mechanical installation must be performed by a qualified installer and in accordance with local, state, and national codes/regulations/laws (if any). 7.2.1 Ensure that the Amtech Streamer Ambient Tower is placed in the best location. Ensure that there is enough serviceable area around the dust collector. It is vital to have at least 36 inches in front of the collector to be able to open the inlets for filter changes. 7.2.2 Ensure that all bolted connections are sealed with a proper sealant. 100% silicone, or other equivalent sealants will be acceptable. 7.2.3 After placement, the collector stand should be secured to the ground with wedge anchor bolts, or equivalent. NOTE: Should questions arise concerning total weight, consult your Clean Air Industries Distributor or Clean Air Industries Factory. 7.3 Electrical NOTE: All electrical installation must be performed by a qualified electrician and in accordance with local, state, and national codes/regulations/laws (if any). 7.3.1 The blower motor is typically configured to operate with 208-230/460 volt, 60 cycles, and 3 phase electrical power, unless specified otherwise with the equipment order. A magnetic motor starter, with overload protection is attached to the unit. The voltage for which the starter control (and motor) is configured should be labeled on the starter control box. The electrical connections to the box (and wiring) must be sized and selected in accordance with local, state, and national codes. 7.3.2 Nominal Full Load Amperes are as follows:
Full Load Current Chart
Voltage
Horsepower
208VAC
230VAC
460VAC
575VAC
10HP 15HP
32.2 48.3
28 42
14 21
11 17
7.3.3 The blower is designed to rotate clockwise when viewed from the motor side (top of blower). If the blower is running in reverse, the air volume will be approximately 50% of the designed air volume and excessive noise will be generated. Therefore, once the motor is wired, check motor rotation by energizing the blower motor for a brief instant (“JOG”). If direction is reversed, then correct. Switching two (2) of the 3-phase connections on the output side will reverse the direction of rotation. 7.3.4 If your unit is equipped with the Turbo Digital Pulse Control, then this feature will need to be connected to a 120VAC power source that is independent of the blower power. A 24VDC pulse controller is available as an option. Power consumption is less than 50 Watts. 7.3.5 If your unit is equipped with any optional electrical features, then these will need to be connected to the appropriate power source. NOTE: Instructions that detail the operation of the Turbo Digital Pulse Control is available under separate cover. A copy of the instructions should have been supplied with the unit.
Page 9
sales@clean-air.com
1-866-665-1829
www.clean-air.com
Made with FlippingBook Digital Proposal Creator