ABR Series performance
M
Q
Q
B
N
J
K
P
P
C
A
E
K
L
J
H
G G F
(2 each end)
D
COMMON DIMENSIONS
J NPT
K NPT 0.50 0.50 0.50 1.00 1.50 2.00 2.00 3.00 3.00 3.00
P NPT
Q NPT 1.50 1.50 1.50 2.50 2.50 3.00 3.00 5.00 5.00 5.00
Weights (lbs.)
Model
F
G
L
M N
A B C D E
H
13 16 18 40 80
0.88 0.88 0.88 1.50 2.00 2.50 2.50 3.50 3.50 3.50
1.94 1.94 1.94 3.62 4.00 4.75 4.75 6.50 6.50 6.50
2.62 2.62 2.62 5.25 6.75 7.50 7.50 8.62 8.62 8.62
3.87 3.87 3.87 3.70 4.05 4.88 4.88 6.52 6.52 6.52
25.62 34.62 43.62 43.00 51.50 50.50 59.60 49.60 58.60 67.60
3.50 3.50 3.50 6.25 7.38 8.81 8.81
29.06 38.06 47.06 48.38 57.62 57.38 66.38 58.38 67.38 76.38
1.72 1.72 1.72 2.89 3.06 3.44 3.44 4.39 4.39 4.39
33.36 42.36 51.36 50.40 59.60 60.25 69.25 62.62 71.62 80.62
2.13 2.13 2.13 3.66 5.13 6.13 6.13 8.00 8.00 8.00
ABR-403-A4-SP ABR-404-A4-SP ABR-405-B4-SP ABR-705-B4-SP ABR-1006-B6-SP ABR-1206-C6-SP ABR-1207-C6-SP ABR-1606-C6-SP ABR-1607-D6-SP ABR-1608-D6-SP
0.41 DIA. 0.44x 1.00 0.44x .88 0.44x 1.00
N/A
N/A
(2) 0.38
130 150 259 270 315
(6) 0.38
(4) 0.50
12.13 12.13 12.13
CAPACITY SELECTION CHART
Rotary 200 0 F Inlet Air
2-Stage 250 0 F Inlet Air
MODEL
P, PSI, In Rated Capacity
P, PSI, In Rated Capacity
SCFM Capacity In Tubes
SCFM Capacity In Tubes
0.15 0.65 2.01 1.65 0.55 0.65 1.95 0.95 1.75 2.10
56 115 200 435 650 950
0.15 0.35 1.25 1.10 0.35 0.35 1.15 0.60 1.10 1.65
45 85
ABR-403-A4-SP ABR-404-A4-SP ABR-405-B4-SP ABR-705-B4-SP ABR-1006-B6-SP ABR-1206-C6-SP ABR-1207-C6-SP ABR-1606-C6-SP ABR-1607-D6-SP ABR-1608-D6-SP
155 315 445 645
1680 2270 3075 3165
1245 1605 2105 2810
PIPING HOOK-UP DIAGRAMS
EXAMPLE
A two stage compressor with a 340 SCFM air delivery at 100psi and a 250 o F discharge temperature. Two psi is the maximum allowable pressure loss. Rate of water flow, to be determined. SELECTION To find a solution, select ABR-1006-B6-SP from the 2-stage column in the above chart. It has a capacity of 445 SCFM. Next, identify the value for P by reading the sub-column within the 2-stage column. The information in that column should be P= 0.35 psi. Data for water flow is 340 SCFM x .035 = 11.9 gpm.
Cooling Water Out
From Compressor
Separator
From Compressor
Cooling Water Out
To Receiver
Air Out
Air In
Cooling Water In
Cooling Water In
Aftercoolers can be mounted in either positions shown. Separators should be used as shown. Consult factory for separator recommendations.
To Receiver
Separator
note: AIHTI reserves the right to make reasonable design changes without notice.