AA & STA Series selection

STEP 4: Calculate the area required

89,090

Q ( btu / hr )

= 17.68 sq.ft.

Required Area sq.ft. =

LMTD c x U ( from table c)

50.39 x 100

STEP 5: Selection a) From table e choose the correct series size, baffle spacing, and number of passes that best fits your flow rates for both shell and tube side. Note that the tables suggest minimum and maximum information. Try to stay within the 20-80 percent range of the indicated numbers. Example Oil Flow Rate = 80 GPM = Series Required from Table E = 1200 Series Baffle Spacing from Table E = 4 Water Flow Rate = 40 GPM = Passes required in 1200 series = 4 (FP) b) From table d choose the heat exchanger model size based upon the sq.ft. or surface area in the series size that will accommodate your flow rate. Example Required Area = 17.68sq.ft Closest model required based upon sq.ft. & series = AA-1224-4-6-FP If you require a computer generated data sheet for the application, or if the information that you are trying to apply does not match the corre- sponding information, please contact our engineering services department for further assistance.

TABLE A- FACTOR M/LMTD = L x M

TABLE D- Surface Area

Surface Area in Sq.ft.

1/4" O.D 3/8" O.D 5/8 O.D Surface Area in Sq.ft.

S/L

M

S/L

M

S/L

M

S/L

M

Model Number

Model Number

1/4" O.D 3/8" O.D

5/8 O.D Tubing

.25 .26 .27 .28 .29 .30 .31 .32 .33 .34 .35 .36 .37 .38 .39 .40 .41 .42 .43 .44 .45 .46 .47 .48 .49

.541 .549 .558 .566 .574 .582 .589 .597 .604 .612 .619 .626 .634 .641 .648 .655 .662 .669 .675 .682 .689 .695 .702 .709 .715

.50 .51 .52 .53 .54 .55 .56 .57 .58 .59 .60 .61 .62 .63 .64 .65 .66 .67 .68 .69 .70 .71 .72 .73 .74

.721 .728 .734 .740 .746 .753 .759 .765 .771 .777 .783 .789 .795 .801 .806 .813 .818 .823 .829 .836 .840 .848 .852 .858 .864

.75 .76 .77 .78 .79 .80 .81 .82 .83 .84 .85 .86 .87 .88 .89 .90 .91 .92 .93 .94 .95 .96 .97 .98 .99

.870 .874 .879 .886 .890 .896 .902 .907 .913 .918 .923 .928 .934 .939 .944 .949 .955 .959 .964 .970 .975 .979 .986 .991 .995

Tubing

Tubing

Tubing

23.55 Tubing

11.78 Tubing

.01 .02 .03 .04 .05 .06 .07 .08 .09 .10 .11 .12 .13 .14 .15 .16 .17 .18 .19 .20 .21 .22 .23 .24

.215 .251 .277 .298 .317 .334 .350 .364 .378 .391 .403 .415 .427 .438 .448 .458 .469 .478 .488 .497 .506 .515 .524 .533

AA-1224

33.76

AA-408

1.35

AA-1236

50.63

35.33

17.66

AA-1248

67.51

47.10

23.55

AA-608

2.62

AA-1260

87.39

58.88

29.44

AA-614

4.58

AA-1272

101.27

70.65

35.33

AA-624

7.85

AA-1284

118.14

82.43

41.21

AA-636

11.78

AA-1296

135.02

94.20

47.10

AA-814

8.55

AA-1624

58.61

41.21

23.55

AA-824

14.65

AA-1636

87.92

61.82

35.33

AA-836

21.2

AA-1648

117.23

82.43

47.10

AA-848

28.3

AA-1660

146.53 103.03

58.88

AA-1672

175.84 123.64

70.65

AA-1014

13.74

9.16

4.58

AA-1684

205.15 144.24

82.43

AA-1024

23.55

15.70

7.85

AA-1696 94.20 AA-16108 263.76 185.46 105.98 AA-16120 293.07 206.06 117.75 234.45 164.85

AA-1036

35.33

23.55

11.78

AA-1048

47.10

31.40

15.70

AA-1060

58.88

39.25

19.63

TABLE E- Flow Rate for Shell & Tube

TABLE B- LMTD correction factor for Multipass Exchangers .05 .1 .15 .2 .25 .3 .35 .4 .45 .5 .6 .7 .8 .9 1.0 .2 1 1 1 1 1 1 1 .999 .993 .984 .972 .942 .908 .845 .71 .4 1 1 1 1 1 1 .994 .983 .971 .959 .922 .855 .70

Shell Max. liquid Flow - Shell Side

Liquid Flow - Tube Side

dia .

Baffle Spacing

SP

TP

FP

Code 1.5 2

3

4

6 Min. Max. Min. Max. Min. Max.

.6 1 1 1 1 1 .992 .980 .965 .948 .923 .840 .8 1 1 1 1 .995 .981 .965 .945 .916 .872 1.0 1 1 1 1 .988 .970 .949 .918 .867 .770 2.0 1 1 .977 .973 .940 .845 .740 3.0 1 1 .997 .933 .835 4.0 1 .993 .950 .850

400

10

19

– 3.5 20

600

15

20 25 30

– 7.5 48 3.5 24

2

12

800

20

35 45 60

10

70 4.5 38

3

21

1000 24

35 60 70

20 120 10 70 5.0 37

R

1200 35

45 70 100 120 30 220 15 112 7.5 56

5.0 1 .982 .917 6.0 1 .968 .885

1600 38

70 150 200 220 57 300 29 180 14

90

8.0 1 .930 10.0 .996 .880 12.0 .985 .720

TABLE C

TUBE FLUID

SHELL FLUID Water 50% E. Glycol Oil 50% E. Glycol Oil

U

14.0 .972 16.0 .958 18.0 .940 20.0 .915

400 350 100 300 90

Water Water Water

50% E. Glycol 50% E. Glycol

K

Copyright © 2019 - 2020 American Industrial Heat Transfer, Inc. note: AIHTI reserves the right to make reasonable design changes without notice. yright © 2017 American Industrial Heat Transfer, I . i t : I I t i t t l i it t ti .

47

I

t i l i

,

t l:

email: sales@aihti.com fax: 434-757-1810 il: l i ti. f :

tel: 434-757-1800 355 American Industrial Drive LaCrosse, VA 23950

Made with FlippingBook - professional solution for displaying marketing and sales documents online