AtkoreMasterElectricalProductsCatalog

PVC Coated Sealing Fittings

Click brand for more product info

EZS Male - Female Hubs

Allied Tube & Conduit Calbond

Features: ꞏ Exterior PVC coating thickness is a minimum 0.040" ꞏ Interior Urethane coating thickness is a minimum 0.002" ꞏ Sizes available are ½" to 3 " ꞏ The length of the sleeve extension(s) shall be at least equivalent to the nominal conduit size for sizes ½"- 2" ꞏ For sizes 2 ½"- 3", the length of the sleeve extension(s) shall be at least 2" ꞏ Mating sealing forms are provided on all caps ꞏ Sealing sleeves on all conduit openings Standards: ꞏ NEC/CEC: EZD 111-611 Class I, Division 1 & 2, Groups C, D Class III ꞏ UL Standard: 1203 ꞏ CSA Standard: C22.2 Applications: ꞏ PVC Coated Sealing Fittings are used in hazardous locations to prevent flame and gas from continuing to travel through the conduit system ꞏ PVC coating provides corrosion protection ꞏ A sealing compound should be used on the interior after wiring ꞏ Compound supplied by the original fitting manufacturer

Part Number

Trade Size

Weight per 100

A

B

Turning Radius

(in)

(lb)

(in)

(in)

(in)

For Sealing in Any Position PV0500EZS16

1/2 3

200 240 300 400 460 690 920 870

4.19 4.19 4.94 5.06 5.19 7.06 7.94 8.63

2.58 2.58 3.08 3.08 3.33 5.27 5.27 5.96

1.88 1.88 2.13 2.31 3.34 3.28 3.38 3.88

PV0700EZS26 PV1000EZS36 PV1200EZS46 PV1500EZS56 PV2000EZS66 PV2500EZS76 PV3000EZS86

1

11 1 1/2

2

21/2

3

Made with FlippingBook - professional solution for displaying marketing and sales documents online