General Fittings
Click brand for more product info
Brackets
Power-Strut Unistrut
P2231A, P2232A
Part Number
“A”
Wt/100 pcs
Vertical Channel
Uniform Design Load
(6.4) 1 ⁄ 4 "
(in)
(mm) (lb)
(kg)
Part Number
Gauge (lb)
(kN)
(88.9) 3 1 ⁄ 2 "
P1000 P1100 P2000 P1000 P1100 P2000
12 14 16 12 14 16
1,600 1,200 800
7.12 5.34 3.56 3.56 2.67 1.78
(27.0) 1 1 ⁄ 16 "
P2231A 6 152.4 191 86.6
A
800 600 400
P2232A 12 304.8 292 132.4
Safety Factor 2 1⁄2
P2233A, P2234A
GR, HG
Part Number
“A”
Wt/100 pcs
Vertical Channel
Uniform Design Load
(6.4) 1 ⁄ 4 "
(in)
(mm) (lb)
(kg)
Part Number
Gauge (lb)
(kN)
(136.5) 5 3 ⁄ 8 "
P1000 P1100 P2000 P1000 P1100 P2000
12 14 16 12 14 16
600 450 300 450 330 220
7.12 5.34 3.56 3.56 2.67 1.78
P2233A 18 457.2 436 197.8
A
(27.0) 1 1 ⁄ 16 "
P2234A 24 609.6 536 243.1
Safety Factor 2 1⁄2
P2513 thru P2516 ꞏ When installed in
Part Number
“A”
Wt/100 pcs
Vertical Channel
Uniform Design Load
inverted position use 60% of loads shown.
(in)
(mm)
(lb)
(kg)
Part Number
Gauge (lb)
(kN)
1,200 800 600
5.34 3.56 2.67 2.67 1.78 1.33 1.78 1.20 0.89 1.33 0.89 0.67
P1000 P1100 P2000 P1000 P1100 P2000 P1000 P1100 P2000 P1000 P1100 P2000
12 14 16 12 14 16 12 14 16 12 14 16
P2513 6 152.4 161 73.0
2" (50.8)
600 400 300 400 270 200 300 200 150
(6.4) 1 ⁄ 4 "
(95.3) 3 3 ⁄ 4 "
P2514 12 304.8 261 118.4
A
P2515 18 457.2 361 163.7
P2516 24 609.6 461 209.1
Safety Factor 2 1⁄2
Standard Dimensions for 1 5⁄8 ” (41.3mm) width series channel fittings (Unless Otherwise Shown on Drawing) Hole Diameter: 9⁄16 ” (14.3mm); Hole Spacing - From End: 13⁄16 ” (20.6mm); Hole Spacing - On Center: 1 7⁄8 ” (47.6mm); Width: 1 5⁄8 ”(41.3mm); Thickness: 1⁄4 ” (6.4mm) with steel meeting or exceeding ASTM A1011 SS GR 33, or 0.220” (5.6mm) with steel meeting or exceeding ASTM A1011 HSLAS GR 45