Power-Strut Unistrut
Transverse Stiffeners
When supporting concentrated loads, the capacity of a pair of slotted-angle beams can be increased by the addition of transverse stiffeners. These should be placed immediately under the load bearing point. The slotted-angle segment used as the stiffener is bolted into place using a metal connector at each junction. Beams that are 6' (182.9 cm) long or less require only one stiffener in the center of the span. Seven-foot beams need two stiffeners placed 2' (61.0 cm) from each end. Eight-foot beams require two stiffeners 2’6" (76.2 cm) from the ends. For beams with a nine-foot span, it is necessary to have three stiffeners at 2’3" (68.6 cm) intervals. Ten-foot beams need three stiffeners with 2’6" spacings.
3'-6'' (106.7 cm) Max.
For maximum effectiveness, transverse stiffeners should never be spaced more than 3’6" (106.7 cm) apart. Note: All loads based on actual physical testing. Documentation available on request.
PA 1SNB — Serrated Nuts and Bolts
Wt/100 pcs: 7 lbs (3.2 kg)