AtkoreMasterElectricalProductsCatalog

Atkore Talon Cable Cleats T1 Cable Cleats

Click brand for more product info

Cope US Tray

Features: ꞏ Optimized for single cables, but may also be used to secure bundles of two or more cables ꞏ Limit cable movement and are easily mounted on ladder-type cable tray, channel strut or structural surfaces ꞏ Utilize a rigid high-strength interlocking frame that simultaneously encloses cables and a support rung

ꞏ LOW SMOKE ZERO HALOGEN — safe for personnel, sensitive electronic equipment and the environment ꞏ 25+ YEARS UV PROTECTION — advanced UV-stabilized material formulation ꞏ RAPID INSTALLATION — lowest total-installed cost ꞏ Made in USA

Table 1A - Cable Range Model – Frame Size

Nominal (Min/ Max) Cable Outer Diameter 1 – Cable 1

Standard (no liner)

C10 Liner 4

C20 Liner 4

C30 Liner 4

C40 Liner 4

(in) 2.0

(mm) 50.8 79.3

(in)

(mm) 45.0 72.0

(in)

(mm) 39.0 70.0

(in) 1.3 2.4

(mm) 33.0 61.0

(in)

(mm) 29.0 54.0

Min Max

1.77 2.83

1.54 2.76

1.14 2.13

T1-05

3.125

Model – Frame Size

Nominal (Min/ Max) Cable Outer Diameter 3 – Cables 2, 3

Standard (no liner)

C10 Liner 4

C20 Liner 4

C30 Liner 4

(in) 1.0 1.3

(mm) 25.4 33.0

(in)

(mm) 25.4 30.0

(in)

(mm) 21.0 28.0

(in)

(mm) 19.0 22.0

Min Max

1.0

0.83

0.75 0.87

T1-05

1.18

1.1

Model – Frame Size

Nominal (Min/ Max) Cable Outer Diameter 4 – Cables 2, 3

Standard (no liner)

C10 Liner 4

C20 Liner 4

C30 Liner 4

(in) 1.0 1.3

(mm) 25.4 33.0

(in)

(mm) 21.0 30.0

(in)

(mm) 19.0 28.0

(in)

(mm) 16.0 22.0

Min Max

0.83 1.18

0.75

0.63 0.87

T1-05

1.1

1. The dimensions listed in the cable range represent the diameter across the outermost layer of the cable (e.g. outer sheath). For application assistance with other cable configurations, contact Atkore. 2. In addition to securing single cables, Atkore Talon® T1 cable cleats may be used to secure bundles of three or more cables. The dimensions listed in the cable range represent the diameter across the outermost layer of each cable (e.g. outer sheath). For application assistance with other cable configurations, contact Atkore. 3. When securing cable bundles of three or more cables in ladder-type cable tray, the rung spacer part number must be confirmed by Atkore. 4. Elastomeric cable cleat liners (a.k.a. inlays) are typically used for cables >35 kV or cables >1000 kcmil. Cable cleat liners may also be used for single and bundled cables that are too small to otherwise fit in a cable cleat frame. Atkore Talon Cable cleat liners are specified by entering the appropriate 3-digit custom feature code in the part number. Refer to Table 3. 5. Other Atkore Talon® cable cleat frame sizes are available on request.

Made with FlippingBook - professional solution for displaying marketing and sales documents online