HCF-Lite ® Aluminum Healthcare Facilities Cable Type AC (120/208V & 277/480V) Technical Specifications Armored Cables (Type AC)
AFC Cable Systems Kaf-Tech Click brand for more product info
Part Number
Trade Size
Grounding Conductor AWG
Approx. Weight/ 1,000 ft
Approx. Armor O.D. (in)
250’ Coil
1000’ Reel
120/208V
2804G42-00
2804G60-00
12-2 Solid (Black, White)
12 Solid (Green)
132
0.545
2805G42-00
2805G60-00
12-3 Solid (Black, Red, White)
12 Solid (Green)
171
0.581
2806G42-00
2806G60-00*
12-4 Solid (Black, Red, Blue, White)
12 Solid (Green)
195
0.621
2807G42-00
2807G60-00
10-2 Solid (Black, White)
10 Solid (Green)
185
0.610
2808G42-00
2808G60-00*
10-3 Solid (Black, Red, White)
10 Solid (Green)
232
0.653
2809G42-00*
2809G60-00*
10-4 Solid (Black, Red, Blue, White)
10 Solid (Green)
279
0.752
120/208V Stranded 2858G42-00
2858G60-00
12-2 Stranded (Black, White)
12 Stranded (Green)
141
0.568
2859G42-00
2859G60-00*
12-3 Stranded (Black, Red, White)
12 Stranded (Green)
171
0.605
2860G42-00*
2860G60-00*
12-4 Stranded (Black, Red, Blue, White)
12 Stranded (Green)
211
0.648
120/208V Specialty Colors 2804G42-04
2804G60-04
12-2 Solid (Red, White)
12 Solid (Green)
132
0.545
2804G42-05
2804G60-05
12-2 Solid (Blue, White)
12 Solid (Green)
132
0.545
480V/277V
2804G42-01
2804G60-01
12-2 Solid (Brown, Gray)
12 Solid (Green)
132
0.545
2804G42-02
2804G60-02
12-2 Solid (Orange, Gray)
12 Solid (Green)
132
0.545
2804G42-03
2804G60-03*
12-2 Solid (Yellow, Gray)
12 Solid (Green)
132
0.545
2805G42-01
2805G60-01*
12-3 Solid (Brown, Orange, Gray)
12 Solid (Green)
171
0.581
2806G42-01
2806G60-01*
12-4 Solid (Brown, Orange, Yellow, Gray)
12 Solid (Green)
195
0.621
480V/277V Stranded 2858G42-01*
2858G60-01*
12-2 Stranded (Brown, Gray)
12 Stranded (Green)
141
0.568
NOTE: All dimensions and weights are subject to normal manufacturing tolerances. Not to be used with set screw type fittings or on DC circuits. * Special Order, Subject to lead time and minimum order quantities
Emergency circuits require special consideration in healthcare settings. Review NEC® 517.30 (C)(3)(3) for guidance on the use of HCF cables on emergency circuits.
Made with FlippingBook - professional solution for displaying marketing and sales documents online