AtkoreMasterElectricalProductsCatalog

TROF

Electrical Grounding & Supports

Electrical Grounding Chart

Table 1 below provides the Minimum Cross Sectional area for two side rails. Using the Fitting Prefix Number (244), the proper value is determined by the Flange Width (column 1), Load Depth, (column 2), and material (column 3). Locate the line containing the Flange Width (column 1) and follow it to the right to the appropriate Load Depth and Material.

Find that value in Table 2, follow it to the right to the Material column to determine the Maximum Ground Fault Amperage.

Table 1

Table 2

Fitting Prefix Number

Min. X-Sect for 2 Rails (NEC Table 392.60(A)

Maximum Ground Fault Amperage (in Amps)

Material

X-Sect Area 0.40 in 2 0.60 in 2 0.70 in 2 1.00 in 2

Aluminum

Steel

Aluminum

Steel

13⁄16 " Flange X-Sect Area

1 1⁄4 " Flange X-Sect Area

13⁄16 " Flange X-Sect Area

1 1⁄4 " Flange X-Sect Area

-

100

1000

-

Flange Load Depth

Material

-

200 400

1200

2 - 13⁄16" 4 - 1 1⁄4"

3" 4" 5" 6"

2 - Mill-Galv 0.60

0.40

3 - HDGAF 4 - Alum.

0.60 0.60 0.40 0.70 0.60 1.00 0.70 0.70 0.60 1.00 0.70 1.00

For Example: If the fitting prefix is 244, the Flange is 13⁄16" , the Load Depth is 4", and the Material is Aluminum. The Minimum Cross Sectional Area (X-Sect Area) is 0.60 in 2 . The Amperage is 1000.

TROF- Electrical Grounding & Supports