Eagle Basket Grounding
Click brand for more product info
Cope US Tray
UL Classified Systems Atkore Eagle Basket systems meet the UL Classification ꞏ Any non-conductive coating to Eagle Basket must be removed by the contractor/
end-user to maintain electrical continuity
STRAIGHT SECTIONS – The grounding of two straight sections requires the use of:
Grounding Clip EGL-GC ꞏ Standard finish is pre-galvanized (PG) ꞏ Sold in packs of 10 ꞏ Connection to splice bars requires a nut and bolt assembly (EG-CBN) purchased separately ꞏ Use on both sides of tray Note: Always place nut on outside of tray
ꞏ (2) EGL-GC ꞏ (2) EG-CBN
These items consist of grounding clips and the appropriate hardware for connecting to trays. One clip should be placed on both sides of the tray, attached at the QUICK- LATCH bar. FITTINGS – Grounding a fitting requires special attention. Typically, fittings are fabricated in the field by cutting straight sections, thus altering the cross sectional area of the tray. A bonding jumper, and/ or a T-BAR, along with the appropriate hardware must be used on either side of the fitting to ensure electrical continuity.
Grounding Wire Split Bolt ꞏ Split bolts are utilized for
SPLIT-BOLT
the attachment of a separate ground wire
ꞏ Use with #6 AWG Ground Conductor Note: Always place nut on outside of tray. EGL-GC must be installed if the tray is to be utilized as an equipment ground conductor.
Bonding Jumper CBJ-C ꞏ Order EGL-GC and
EG-CBN separately for installation