Armored Fire Alarm/Control Cable
AFC Cable Systems Kaf-Tech Click brand for more product info
Fire Alarm / Control Cable TM – Type FPLP Plenum Rated Technical Specifications
Maximum Voltage Rating ꞏ 300V References & Ratings ꞏ UL 66, 1424, 1479, 1569, 1581, 2556, File Reference E83514 ꞏ NEC ® 300.22(C), 392, 501, 502, 503, 504, 505, 518, 530, 645, 725, 760.154(A) ꞏ NEC ® 300.22 (C) Other Spaces Used For Environmental Air (Plenums) ꞏ NFPA 262 (formerly UL 910) Plenum Rated - Type FPLP ꞏ UL classified 1, 2, and 3, hour through (Fire) penetration product R14141 ꞏ Cable tray rated, install per NEC ® ꞏ Federal Specification A-A-59544 (formerly J-C-30B) ꞏ Meets all applicable OSHA and HUD requirements ꞏ May be surface mounted, fished and /or embedded in plaster ꞏ Made in USA of US and /or imported materials
Drain Wire
Mylar® Shield
Copper Conductors
TFN Insulation
Armor ꞏ Interlocked Galvanized Steel Strip (Red) Conductors ꞏ Solid Copper Conductor Insulation ꞏ TFN 16 AWG Assembly ꞏ Polyester Assembly Tape; Twisted Shielded: Laminated Aluminum/Mylar ® Shield with Tinned Copper Drain Wire Maximum Temperature Rating
ꞏ FPLP: 105°C (Dry) Neutral Conductor ꞏ White (Where Applicable)
Part Number
Trade Size
Grounding Conductor AWG
Approx. Weight/ 1,000ft
Approx. Armor O.D.
250' Coil
1000' Reel
(lb)
(in)
SOLID TFN
N/A
195
0.627
1843R42-00
1843R60-00
16-4 (2 TSP) (Black, White) (Red,Blue) 1
*Special Order, subject to lead limes and minimum order quantities ¹ All drain wires are 18AWG tinned Copper in TSP construction