AtkoreMasterElectricalProductsCatalog

Armored Fire Alarm/Control Cable

AFC Cable Systems Kaf-Tech Click brand for more product info

MC Glide Fire Alarm/Control Cable TM – Type FPLP Plenum Rated Technical Specifications

Maximum Voltage Rating ꞏ 300V References & Ratings ꞏ UL 66, 1424, 1479, 1569, 1581, 2556, File Reference E83514 ꞏ NEC ® 300.22(C), 392, 501, 502, 503, 504, 505, 518, 530, 645, 725, 760.154(A) ꞏ NEC ® 300.22 (C) Other Spaces Used For Environmental Air (Plenums) ꞏ NFPA 262 (formerly UL 910) Plenum Rated - Type FPLP ꞏ UL classified 1, 2, and 3, hour through (Fire) penetration product R14141 ꞏ Cable tray rated, install per NEC ® ꞏ Federal Specification A-A-59544 (formerly J-C-30B) ꞏ Meets all applicable OSHA and HUD requirements ꞏ May be surface mounted, fished and /or embedded in plaster ꞏ Made in USA of US and /or imported materials ꞏ US Patent 11,101,056 & D935,731

Interlocked Galvanized Steel Strip

Drain Wire Copper Conductors

TFN Insulation

Mylar ® Shield

Armor ꞏ Interlocked Galvanized Steel Strip (Red) Conductors ꞏ Solid Copper Conductor Insulation ꞏ TFN 16 AWG Assembly ꞏ Polyester Assembly Tape; Twisted Shielded: Laminated Aluminum/Mylar ® Shield with Tinned Copper Drain Wire Maximum Temperature Rating

ꞏ FPLP: 105°C (Dry) Neutral Conductor ꞏ White (Where Applicable)

Part Number

Trade Size

Grounding Conductor AWG

Approx. Weight/ 1000ft

"Approx. Armor O.D

250' Coil

1000' Reel

(lb)

(in)

SOLID TFN SF60R42-00

N/A

122

0.435

SF60R60-00

16-2 (TSP) (Black, White) 1

*Special Order, subject to lead limes and minimum order quantities ¹ All drain wires are 18AWG tinned Copper in TSP construction