Liquidtight Flexible Metal Conduit
Click brand for more product info
UL and CSA Low Smoke Zero Halogen Cable – Type LSZH, LFMC
AFC Cable Systems Kaf-Tech
Part Number
Trade Size
Trade Size
Coil Length
Reel Length
Approx. Weight/100 Ft
External Diameter Over Conduit Min/Max
External Diameter Over Jacket Min/Max
Internal Diameter Min/Max
Bend Radius
(in)
(mm)
(ft)
(ft)
(lb)
(in)
(in)
(in)
(in)
3/8 1/2 1/2 1/2 3/4 3/4 3/4
12 16 16 16 21 21 21 27 27 35 35 35 41 53 63
100 100
— —
24 31 31 31 47 47 47 78 78
0.594 /0.614 0.690 /0.710 0.484 /0.504 2.00 0.732 /0.765 0.820 /0.840 0.622 /0.642 3.25 0.732 /0.765 0.820 /0.840 0.622 /0.642 3.25 0.732 /0.765 0.820 /0.840 0.622 /0.642 3.25 0.930 /0.960 1.030 /1.050 0.820 /0.840 4.25 0.930 /0.960 1.030 /1.050 0.820 /0.840 4.25 0.930 /0.960 1.030 /1.050 0.820 /0.840 4.25 1.201 /1.226 1.290 /1.315 1.041 /1.066 6.50 1.201 /1.226 1.290 /1.315 1.041 /1.066 6.50 1.540 /1.570 1.630 /1.660 1.380 /1.410 8.00 1.540 /1.570 1.630 /1.660 1.380 /1.410 8.00 1.540 /1.570 1.630 /1.660 1.380 /1.410 8.00 1.735 /1.770 1.865 /1.900 1.575 /1.600 9.00 2.180 /2.215 2.340 /2.375 2.020 /2.045 11.12 2.640 /2.675 2.840 /2.875 2.480 /2.505 14.62
6701-30-00 6702-30-00 6702-45-00 6702-60-00 6703-30-00 6703-45-00 6703-60-00 6704-30-00 6704-41-00
— —
500
1000
100
—
— —
500
1000
1 1
100
—
—
400
6705-24-00 1 1/4 6705-40-00 1 1/4 6705-47-00 1 1/4 6706-24-00 1 1/2
50
—
102 102 102 107 144 168
— —
200 750
50 50 25
— — —
6707-24-00
2
6708-22-00 2 1/2
Note: All dimensions and weights are subject to normal manufacturing tolerances. Review NEC® 350.60 and 250.118(6) for grounding requirements.
Combustion and Flammability Properties Property
Test
Results
Vertical Burn (Material) Vertical Burn (Conduit) Oxygen Index % (Material)
UL 94
UL Listed: V-O Rating No FlaMing Drips
UL 360
UL Listed: Passed
ASTM® D 2863 ASTM® E-162
25%
Flame Spread Index
PassedNo FlaMing Drips
Smoke Generation (FlaMing) Smoke Generation (Non-flaMing)
ASTM® E662 (NFPA-258) ASTM® E662 (NFPA-258) Bombardier SMP-800C
Ds=13 @ 1.5 Min Ds=57 @ 4.0 Min No FlaMing Drips Ds=1 @ 1.5 Min Ds=8 @ 4.0 Min No FlaMing Drips
Toxic Gas Generation
Pass
Testing performed by independent test laboratory. Test results available upon request.
Made with FlippingBook - professional solution for displaying marketing and sales documents online