Clean Air America WeldStation Basic User Manual

O PTION M ODE : R UN P LS DEL P

“Run Pulse Limit” - This option sets the pressure differential at which the running pulse sequence will be activated in Automatic Mode (see Auto Mode: Above). This pulsing state is referred to as the online cleaning cycle. To change the value, press the ‘OK’ button. The number of pressure value will begin to flash. Use the ‘+’ and ‘-’ buttons to increase and decrease the amount of cycles respectively. Press the ‘OK’ button again to set the counter value.

O PTION M ODE : A LARM DEL P

“Alarm Limit” - This option sets the pressure differential at which the filter cleaning alarm will be activated in Automatic Mode (see Auto Mode: Above). To change the value, press the ‘OK’ button. The number of pressure value will begin to flash. Use the ‘+’ and ‘-’ buttons to increase and decrease the amount of cycles respectively. Press the ‘OK’ button again to set the counter value.

O PTION D EFAULTS

The Weld Station will arrive preprogrammed with no necessary adjustments needed. The Option Modes allow for the changing of some variables, which may extend filter life or increase performance on non-standard applications.

If the settings are changed, the defaults are as follows:

Option Mode: ShutDown Pls #:

05

Option Mode: Shutdwn delP:

3.0

Option Mode: Run Pls delP:

7.0

Option Mode: Alarm delP:

9.9

Copyright © Clean Air America, Inc.

Weld Station User Manual, March 2011