Practical Pointers | Fives North American

PREMIX SYSTEMS

control valve

optional cross-connected impluse line if higher mixture pressure is required*

air

5 D

3 D

flame

8 osi

4 1/2 "w.c.

4"w.c.

gas

Limiting Orifice

gas pressure = zero (if no impulse) or equal to air impulse if used

required gas pressure = pressure drop through regulator + safety factor + air impulse (when used)

PREMIX SYSTEM IN USE

As restriction in the mixture line is increased, the mixture pressure will rise and the suction will be reduced. If the restriction is sufficient to cause the suction to be too low to supply enough gas, a smaller capacity mixer and rod (or less outlet restriction) is required. Mixture piping should be sized for a low pressure drop, 0.5"w.c. or less. In a typical installation, the regulator would be sized for a minimum 2 osi drop, and a safety factor of 1 osi would be allowed, requiring a gas supply pressure to the regulator inlet of 3 osi (See page 24 for detailed sizing instructions). * If necessary the 7218 Regulator may be cross-connected to the air or mixture line to overcome the effect of high restriction in the mixture line or nozzle.

13

Made with FlippingBook - Online catalogs