Practical Pointers | Fives North American

NOZZLE MIX SYSTEMS

air

16 osi

3D

5D

4 pipe dia.

2 osi minimum drop

10 pipe dia.

19 osi

16 osi

16 osi

GAS PRESSURE REQUIREMENTS FOR CROSS-CONNECTED AIR/GAS RATIO REGULATORS

Operation of this system depends on an adequate gas supply pressure. With 16 osi impulse the regulator will open until an outlet pressure of 16 osi is reached. If the regulator is sized to take a 2 osi pressure drop at full fire conditions, an inlet pressure of 18 osi or more is required. A little extra inlet pressure is desirable as a safety factor; thus . . .

Air pressure..................................................................16 osi Pressure drop through regulator.............................. 2 osi Safety factor................................................................. 1 osi Required supply pressure . 19 osi or, if a regulator is sized for a 6 osi drop............16 osi 6 osi 1 osi 23 osi

32