Practical Pointers | Fives North American

NOZZLE MIX SYSTEMS

R

bleeder set for 50%

M

A

air

combustion chamber

± 2 osi

*

4 pipe dia.

10 pipe dia.

EFFECT OF PRESSURE OR SUCTION IN COMBUSTION CHAMBER ON CONTROL WITH A CROSS-CONNECTED SYSTEMWITH BLEEDER

A 2 osi combustion chamber pressure or suction is imposed on top of the diaphragm, but, without line (M), the bleeder reduces it to 50% or 1 osi on the bottom of the diaphragm. To correct this condition the bleed opening should be connected to the burner mounting by line (M).

* See page 9 for location of combustion chamber pressure tap

36