Practical Pointers | Fives North American

PILOT SYSTEMS

NATURAL GAS FLAMES OF A 4011 PREMIX PILOT SET (4021 Pilot Tip with 4031 Pilot Mixer)

operating with 16 osi air, 7"w.c. mixture pressure (30,000 Btu/hr)

at stoichiometric air/fuel ratio

1 2 3 4 5 6  7 8  9 10 11

with 25% excess air (lean)

1 2 3 4 5 6  7 8  9 10 11

with 15% excess fuel (rich)

1 2 3 4 5 6  7 8  9 10 11

With 3"-4"w.c. mixture pressure (6-8 osi air--all available with 8 osi blower), flames are approximately 2/3 of length scaled, for 7"w.c.

For a 4015 Pilot Set (4025 Pilot Tip and 3065 Aspirator Mixer), flame length is 13"-14" with 16 osi air at the mixer, operating at stoichiometric air/fuel ratio.

53