Shut Down Pulse Pressure Setting - This option sets the pressure differential at which the shut pulse down sequence will be activate. Once this pressure is reached, the unit will pulse when the motor is stopped
This values is measured in inches of water column (in. H 2 O).
This pulsing state is referred to as the offline cleaning cycle.
To change the value, use the 'Increment Up' and 'Increment Down' buttons to change the setting by 0.1 in. H 2 O. By touching the numerical display, a keypad will appear on the screen which can be used to enter the number directly.
Running Pulse Pressure Setting - This option sets the pressure differential at which the running sequence will be activate while the unit is running.
This values is measured in inches of water column (in. H 2 O).
This pulsing state is referred to as the online cleaning cycle.
To change the value, use the 'Increment Up' and 'Increment Down' buttons to change the setting by 0.1 in. H 2 O. By touching the numerical display, a keypad will appear on the screen which can be used to enter the number directly.