B LOWER R OTATION
If blower rotation is incorrect, the unit will suffer a significant performance loss as well as an increase in noise level. Make sure the blower is rotating properly. To check blower rotation, have a colleague start the unit, count to '4', and then stop unit. As the fan slows, watch the rotation. When power is properly connected, the blower will rotate counter-clockwise when viewed from the exhaust of the Dual WeldStation unit. Make sure to check rotation from the exhaust (top) side. To change the blower rotation direction, simply swap any (2) of the incoming power leads.
PLEASE NOTE: IT IS VERY IMPORTANT TO VIEW THE ROTATION
FROM THE EXHAUST OF THE Dual WeldStation !