Clean Air Industries WeldStation EVO User Manual

A PPENDIX D: W IRING D IAGRAMS (D ECEMBER

2019+)

Notes concerning the wiring diagram:

Power is brought into the electrical box as 460 / 230 / 208 Volt AC three phase or 230 / 208

Volt AC single phase. Power is then branched to the transformer via a single phase. This

transformer converts the 460 / 230 / 208 Volt AC single phase to 120 Volt AC single phase.

This is then branched to 24V DC for the controller, LED lights, and air sensors.

Breakers are marked on the electrical diagram. There are:

(1) on the transformer secondary coil

(2) on the transformer primary coils.

(1) on the terminal strip for the differential pressure sensor

(1) on the terminal strip for the lighting circuit

The overload may need to be reset. The Eaton overloads have an automatic reset function,

which is turned off. If this has not been set, the overload will require being reset via the red

button marked 'Reset'.

A unit can be wired for both High Voltage (460 VAC 3 Phase) and Low Voltage (230 / 208

VAC 3 Phase). The jumper(s) on the input 'H' side of the transformer change depending on

the input voltage. For changing the wiring of the unit, refer to the wiring diagram for jumper

settings and motor wiring.

NOTE:

If the unit is being changed from High to Low Voltage (or vice versa), the

contactor and overload may need to be changed. This is because the lower

voltage requires twice the amperage. If the unit is being converted to low

voltage, the power wiring should be checked for proper gage wires. The

wiring in the motor connection must be changed as well.

Wire numbers have been added to the wiring diagram to aid in both the diagnostic issues as

well as the maintenance and service issues while in the field.

Page 82 of 83

1-866-665-1829

clean-air.com

sales@clean-air.com

Made with FlippingBook - professional solution for displaying marketing and sales documents online