Mole Energy - Surveyors Manual - Digital PDF - AW4

Backup Gateway 2 POWER WALL

Backup Gateway 2 for Tesla Powerwall provides energy management and monitoring for solar self-consumption, time-based control, and backup operation. When the Powerwall system is in Backup mode, Backup Gateway 2 controls connection to the grid, automatically detecting outages and providing seamless transition to backup power. Communicating directly with Powerwall, Backup Gateway 2 allows you to monitor energy use and manage backup energy reserves from any mobile device with the Tesla app.

PERFORMANCE SPECIFICATIONS

MECHANICAL SPECIFICATIONS

AC Voltage (Nominal)

Dimensions

240 V (Line-to-Neutral) 440 V (Line-to-Line)

584 mm x 380 mm x 127 mm (23 in x 15 in x 5 in)

Feed-In Type

Weight

Single Phase, Three Phase

11.4 kg (25.1 lb)

Grid Frequency

Breaker space (DIN rail)

50/60 Hz

Main breaker: 1-, 2- or 3-pole Generation/Load breakers: 6 spaces

Nominal Current

100 A per phase (Single Phase) 80 A per phase (Three Phase)

Mounting options

Wall mount

Maximum Input Short Circuit Current 16 kA 1

380 mm (15 in)

127 mm (5 in)

Overvoltage Category

Category III

AC Meter

Revenue accurate (+/– 0.2 %) 2

Connectivity

Ethernet, Wi-Fi, Cellular (LTE/4G) 3

User Interface

Tesla App or Local Network Monitoring

Operating Modes

Support for solar self-consumption, time-based control, and backup Backup of selected single phase; Automatic disconnect of all phases Supports up to 10 AC-coupled Powerwalls

Backup Operation

584 mm (23 in)

Modularity

Warranty

10 years

1 16 kA rating when installed with DIN-mount fuse; 10 kA rating without fuse. 2 Revenue accurate when using Gateway internal site meter. 3 Cellular connectivity subject to network operator service coverage and signal strength (2G/3G supported where LTE/4G unavailable).

COMPLIANCE INFORMATION

ENVIRONMENTAL SPECIFICATIONS

Safety

Operating Temperature

IEC 62109-1, IEC 62053-22, IEC 61439-1, IEC 61439-3 EMC Directive 2014/30/EU, Radio Equipment Directive 2014/53/EU, IEC 61000-6-1, IEC 61000-6-3, EN 55024, EN 300 328, EN 300 440,

–20°C to 50°C (–4°F to 122°F)

Operating Humidity (RH)

Up to 100%, condensing

EMC and Radio Equipment

Maximum Elevation

3000 m (9843 ft)

Environment

Indoor and outdoor rated

Ingress Rating

IP55

EN 301 489-1, EN 301 489-17, EN 301 489-52, EN 301 511, EN 301 893, EN 301 908-1 RoHS Directive 2011/65/EU, WEEE Directive 2012/19/EU, Battery Directive 2006/66/EC REACH Regulation EC 1907/2006

Environmental

Seismic

AC156, IEEE 693-2005 (high)

ROW-UK 2019-06-18

TESLA.COM/ENERGY

Go Back

11