Technical data 3.0/3.6/4.0 kW
Primo GEN24/GEN24 Plus
3.0
3.6
4.0
2
2
2
Number of MPP trackers
DC input voltage range (Udc min - Udc max)
65 - 600
65 - 600
65 - 600
V
400
400
400
Nominal input voltage (Udc,r)
V
Feed-in start-up input voltage (Udc start)
80
80
80
V
65 - 530
65 - 530
65 - 530
Usable MPP voltage range
V
MPP voltage range (at rated power) (Umpp min - Umpp max)
190 - 530
200 - 530
210 - 530
V
MPPT1
MPPT2
MPPT1
MPPT2
MPPT1
MPPT2
22
12
22
12
22
12
Max. usable input current (Idc max)
A
36
19
36
19
36
19
Max. array short circuit current (Isc pv) 1
A
2
2
2
2
2
2
Number of DC connections
MPPT1 MPPT2 Total
MPPT1 MPPT2 Total
MPPT1 MPPT2 Total
W 3,110 3,110 3,110 3,810 3,810 3,810 4,140 4,140 4,140
Max. usable DC power
3,750 3,110 4,500 4,600 3,810 5,520 5,000 4,140 6,000
Max. PV generator output
Wpeak
3,000
3,680
4,000
AC rated power (Pac,r)
W
3,000
3,680
4,000
Apparent power
VA
3,000
3,680
4,000
Max. output power
VA
220 Vac
230 Vac
220 Vac
230 Vac
220 Vac
230 Vac
13.6
13
16.7
16
18.2
17.4
Nom. AC output current
A
1~ NPE 220/230 (+20%/-30%)
Grid connection (Uac,r)
V
Frequency (frequency range fmin - fmax)
50/60 (45 - 65)
Hz
< 2
< 2
< 2
Total harmonic distortion
%
0,8 - 1 ind. / cap.
Power factor (cos φ ac,r)
3,000
3,000
3,000
Nom. output power PV Point
VA
1~ NPE 220/230
Grid connection PV Point
V
< 23
< 23
< 23
Switching time
sec.
Full Backup power and battery function only available with GEN24 Plus
Primo GEN24 Plus
3.0
3.6
4.0
3,000
3,600
4,000
Nom. output power Full Backup
VA
1~ NPE 220/230
Grid connection Full Backup
V
< 35
< 35
< 35
Switching time
sec.
1
1
1
Number of DC inputs
22
22
22
Max. input current (Idc max)
A
DC input voltage range (Udc min - Udc max) 3
150 - 455
150 - 455
150 - 455
V
1x BATT+ and 1x BATT- push-in spring terminals 2.5 - 10 mm²
DC battery connection technology
3,110
3,810
4,140
Max. DC input/output power 4
W
3,000
3,680
4,000
Max. charging power for AC coupling 4
W
BYD Battery-Box Premium HVS/HVM, LG FLEX 6
Compatible batteries 5
1 Isc pv = Isc max >= Isc (STC) x 1,25 according to e.g. IEC 60364-7-712, NEC 2020, AS/NZS 5033:2021. 2 The Full Backup option is available for the Primo GEN24 3.0–6.0 Plus. Additional external components for grid switchover are required for the Full Backup. See the Operating Instructions for further details. 3 AC power derating of the inverter occurs with a DC battery input voltage of 419.7 V and higher 4 Depending on connected battery 5 Depending on the country-specific certification and availability 6 Excluding BYD Battery-Box Premium HVS 10.2, HVS 12.8, HVM 8.3, HVM 22.1 & LG FLEX 17.2
Go Back
19