ATHLETIC FACILITIES REPORT June 18, 2015

FACILITY INFORMATION Name / Address :

Manufacturer :

Year Constructed :

Square Footage :

UBU Sports Surfaces

2010

89,000

District ’s Stadium Greencastle-Antrim SD 500 E. Leitersburg Street Greencastle, PA 17225

In-Fill Make-Up :

Fiber :

Base :

Turf Height :

Rubber

Monofiliment Stone w/Pad

±2.25” (at install)

Weather Conditions: Start: Partly Sunny, 79°

Field Temp.

Start: 119.37° Finish: 104.33°

Finish: Cloudy, 79°

WORK COMPLETED

Service :

Date Completed

G-Max Testing

06.17.2015

In accordance with ASTM F355-10a and F1936-10 Equipment: Triax 2010 Surface Impact Tester

G-MAX TEST RESULTS SUMMARY

Synthetic Turf :

High Point - # 1 Low Point - # 2

144 G

 

119 G Overall field G-max Average:

129.90 G

(Based on the 10 locations required for testing).

High Point - # 2 Low Point - # 1

1.35 ” 1.10 ”

 

Infill depth average:

1.23 ”

(Based on the 10 locations required for testing).

OBSERVATIONS / RECOMMENDATIONS

1.) All test points met the requirement of <200 average g-max when tested in accordance with ASTM F355-10a and F1936-10. 2.) Approximately 20 locations of seam separation noted when conducting service. Recommend comprehensive field review and repair of all identified seams. 3.) Continue to monitor fiber wear. 4.) Field conditioning / deep cleaning recommended for infill distribution, and remove hard and fine contaminants. 5.) Relocate all practice events away from goal creases, use only for competition events. 6.) Field is in its 5 th year of use. Expected field life is 8-12 years. 7.) Annual G- max testing is recommended to monitor the safety of the field’s playability. Testing should be in conformance with ASTM F355-A and ASTM F1936. Annual testing will provide regulated assessment of field condition.