BlueCool F-Series Fresh air makeup units
BlueCool F-Series Fresh air systems
Compact, highly efficient EC-motor
Fresh air systems BlueCool F-Series fresh air systems are the ideal complement to your central chiller system. Fresh outside air is filtered and cooled before it is brought into the cabin at the ideal comfort temperature. Stale air is extrac - ted and transported to the outside. A sophisticated control concept of cooling and heating ensures the ideal condition of temperature and humidity.
Removable covers for instant access and easy servicing
Standardized hose connector
High grade F7 filter (optional)
Acoustics-optimized system components for use in particularly noise-critical applications
Control elements for BlueCool F-Series (FreshAir) Please select the control elements for the core unit separately: Control Box F-Series F500-F2000 See page 142
Technical data
BlueCool Fresh Air and Extract
F500 FreshAir
F1000 FreshAir
F2000 FreshAir
F500 Extract
F1000 Extract
F2000 Extract
2510265A
2510266A
2510267A
2510268A
2510269A
2510270A
Part No.
500 294
1,000
2000 1,177
500 294
1,000
2,000 1,177
Air flow (300 Pa) (m³/ h) Air flow (300 Pa) (cfm) Cooling capacity (kBTU / h)
588
588
21
42
84
– – – – – – – –
– – – – – – – –
– – – – – – – –
6.0
12.0
25.0
Cooling capacity (kW)
21
42
84
Heating capacity ‘chilled’ water (kBTU / h) Heating capacity ‘chilled’ water (kW) Heating capacity electric (kBTU / h) Heating capacity electric (kW)
NEW
6.0 5.0 1.5
12.0 10.0
25.0 20.0
The BlueCool F-2000 Fresh Air can also be used as a large, silent air handler in combination with the Cabin Control Kit A-Series.
3
6
26
52 15
104
Heating capacity total (kBTU / h) Heating capacity total (kW)
7.5
31
230
230
230
230
230
230
Voltage (V)
50 / 60
50 / 60
50 / 60
50 / 60
50 / 60
50 / 60
Frequency (Hz)
9.1
16.8
32.5
–
–
–
Current draw cooling (A) 50 + 60 Hz max.
Higher air flow 3 variants for 500 up to 2,000 m³ / h fresh air and extract air. All units are operating with high efficiency EC-blower with high back pressure resistance. High cooling capacity Increased cooling capacity by up to 75 % compared to previous fresh air system. Cooling capacity with up to 84 kBTU / h. Ideal solution for larger yachts. Compact design Standardized and compact design. High efficiency air filters Equipped with standard air filter of category G3. High grade F7 filter available for easy exchange. Improved climate control logic Constant supply air temperatures with integrated solenoid proportional valve and up to 20 kBTU / h staged electrical heating. Acoustics – optimized components for use in particularly noise-critical applications.
9.1
16.8
32.5
–
–
–
Current draw heating (A) 50 + 60 Hz max. (‘chilled’ water + electric)
0.8 2.1 2.1
1.4 3.9 3.9
2,7 7.5 7.5
0.8
1.4
2.7
Current blower (A)
– – – – –
– – – – –
– – – – –
Power consumption heating (kW) Power consumption cooling (kW) Chilled water connection (mm) Chilled water connection (Inch) Minimum chilled water flow ( l / min)
DN20
DN25
DN32 1 1/ 4
3 / 4
1
18
37
73
720 x 400 x 500 760 x 550 x 650 930 x 700 x 750 320 x 320 x 320 450 x 450 x 450 600 x 600 x 600
Dimensions L x H x W (mm) Dimensions Lx H x W (inch)
28.3 x 15.7 x 19.7
29.9 x 21.7 x 25.6 36.6 x 27.6 x 29.5 12.6 x 12.6 x 12.6 17.7 x 17.7 x 17.7 23.6 x 23.6 x 23.6
150
2x 150
315 12.5 315 12.5 110
150
200
315 12.5 315 12.5
Discharge connection diameter (mm) Discharge connection diameter (inch) Suction connection diameter (mm) Suction connection diameter (inch)
6
7.5
6
7.5
150
200
150
200
6
8
6
8
42
65
25
35
60
Weight Unit (kg)
7
7
7
–
–
–
Weight electrical box (kg)
120
121
Made with FlippingBook Digital Proposal Creator