PRODUCT CATALOGUE 2023 | alre.de

AIR CONDITIONING TECHNOLOGY

ELECTRONIC CLIMATE CONTROLLER, KTRRB SURFACE-MOUNTED INSTALLATION – BERLIN 3000

TECHNICAL DATA

APPLICATION

Design:

Berlin 3000

Single-room temperature controller with neutral zone for 2-pipe or 4-pipe air conditioners.

Surface finish: Housing colour: Housing material: Operating voltage:

matt

pure white, similar to RAL 9010

ABS plastic

External flow sensor (H / C sensor): for switching automatically

230 V AC, 50 Hz

Ambient temperature: Storage temperature: Permissible atmospheric humidity: Electrical connection: Mounting / attachment:

0 to 40 °C

of the controller to heating or cooling mode in 2-pipe operation depending on the inflow temperature; alternatively, this input can be used as an H / C changeover contact. Sensor rupture and short-circuit fuse: in case of a sensor rupture or sensor short-circuit, the heating is activated with a power-on time of 30% to prevent cooling or frost damage in the room.

−20 to +70 °C

max. 95% rel. humidity, non-condensing screw-type terminals

surface / wall mounting or by means of an adapter plate on a flush-mounted socket

Protection rating: Protection class: Safety and EMC:

IP30

II, if properly mounted

according to DIN EN 60730

Max. switching voltage: Min. switching voltage:

230 V AC, 50 Hz 230 V AC, 50 Hz

Switching element: Switching contact:

relay

NO contact

Output signal:

switching (230 VAC, 50 Hz)

Sensor:

internal NTC, optional external NTC ‘Sensor 2’ reduction by 3 K; alternatively, this input can be configured as a frost protection contact

ECO contact*:

Control function: Control range:

heating and / or cooling

5 to 30 °C approx. 2 K

Neutral zone:

General features:

operating mode ‘off with frost protection monitoring’; mechanical range restric- tion; scale: degrees Celsius; external setting

TYPE / IMAGE

ITEM NO.

FEATURES

EURO / PG

KTRRB-117.128

General features: single-room climate controller, 3-stage fan output, fan operation in neutral zone ON / OFF selectable; on / off switch; 3-stage fan switch

MA601300

201.40 / I

Max. switching current: heating 5 (1) A, cooling 5 (1) A, fan 3 (1) A Switching power: heating 1150 W, cooling 1150 W, fan 230 W Hysteresis: approx. 1 K

KTRRB-117.163

MA601400

Similar to KTRRB-117.128 but without 3-stage fan output and 3-stage fan switch

193.10 / I

KTRRB-117.169

General features: single-room climate controller; ‘off / manual fan / automatic fan’ switch; ‘ventilator 3-stage 0–10 V’ switch; ‘parametrisation 3-stage fan output’ button; ‘heating, cooling, frost protection, sensor rupture or short circuiting of the external sensor’ display; 3-stage fan output 0–10 V with adjustment to individual fan stages or dynamic 0–10 V to activate EC fans ;

MA601500

210.80 / I

ON / OFF: ventilator operation in neutral zone selectable Max. switching current: heating 5 (1) A, cooling 5 (1) A Switching power: heating 1150 W, cooling 1150 W Output signal: Analogue 0–10 V (5 mA) for activating an rpm-controlled fan Hysteresis: approx. 0.5 K

Accessories: Adaptor plate for mounting on flush-mounted socket JZ-17, terminal strips VOOxx (see Page 130 , Page 165), suitable valve actuators ZBOOA-010.1xx (see Page 168 +Page 169, suitable external sensors (‘sensor 2’; see ‘Sensor technology’) You can find other / similar controllers with outputs for heating / cooling in the ‘Heating technology’ section (RTBSB / RTBSU).

*With ECO operation, the neutral zone (2 K) is extended by the ECO zone (+ / – 3 K). ECO operation is a savings mode that should be controlled, for example, via a window contact and / or a timer.

142

Catalogue 2023

Made with FlippingBook Annual report maker