PLANT ENGINEERING
SINGLE-STAGE PLANT ROOM THERMOSTATS JET-110/-120 CAPILLARY SYSTEM – EXTERNAL SENSORS – CONFIGURABLE HYSTERESIS
TECHNICAL DATA
APPLICATION
Colour:
grey (lower part similar to RAL 7016, upper part similar to RAL 7035) Max. 95% rel. humidity, non-condensing
Control or monitoring of the tem- perature in the industrial domain in a non-aggressive environment, for exam- ple, for controlling heating or cooling systems in greenhouses, industrial and sports halls, air-inflated domes, cold storage and refrigeration rooms.
Permissible atmospheric humidity:
Operating voltage:
none
Max. switching current: Min. switching current: Max. switching voltage: Min. switching voltage: Switching element: Switching contact: Control function: Electrical connection: Mounting / attachment:
10 (4) A 150 mA
230 V AC, 50 Hz 24 VAC, 50 Hz
The JET-110 RF is particularly suitable as an external thermostat.
microswitch
For successor types for JET-4x and JET-4x F see pageSeite 182 (plant room thermostat RTKSA)
toggler, potential-free heating or cooling screw-type terminals
wall mounting
Protection class: Protection rating: Safety and EMC:
I
IP65
according to DIN EN 60730
Sensor:
liquid-filled capillary
Sensor material: General features:
Cu
scale: degrees Celsius
TYPE
ITEM NO.
CONTROL RANGE
MAX. SENSOR TEMPERATURE
HYSTERESIS (APPROX.)
AMBIENT TEMPERA- TURE
FEATURES
EURO / PG
JET-110 R
JA045100
−35 to +30 °C 35 °C
2 – 20 K adjustable 2 – 20 K adjustable 2 – 20 K adjustable 2 – 20 K adjustable
−35 to +35 °C
External setting with range restriction, TR Internal setting with viewing window, TW External setting with range restriction, TR Internal setting with viewing window, TW
156.20 / II
JET-110 RF
JA045200
−35 to +30 °C 35 °C
−35 to +35 °C
156.90 / II
JET-120 R
JA046100
0 to 60 °C 70 °C
−35 to +70 °C
156.20 / II
JET-120 RF
JA046200
0 to 60 °C 70 °C
−35 to +70 °C
157.00 / II
TR = temperature controller, TW = temperature monitor
ILLUSTRATIONS
JET-1x0 RF
JET-1.
JET-1.
193
Catalogue 2023