PRODUCT CATALOGUE 2023 | alre.de

PLANT ENGINEERING

SINGLE-STAGE CAPILLARY THERMOSTATS JET-1

TECHNICAL DATA

APPLICATION

Housing colour:

grey (lower part similar to RAL 7016, upper part similar to RAL 7035) Cu (capillaries made from V2A) 1.8 m (for types with ‘G’ in the type specification: 4.5 m)

Monitoring or control of temperatures of non-aggressive, liquid and gaseous media. Particularly suitable for wall mounting. The SW-200-12 protecting coil is to be used for temperature con- trol of non-aggressive gases in ducts; for temperature control in non-ag- gressive fluids, use the TH immersion sleeve, and in aggressive fluids, the NTH immersion sleeve. Immersion sleeves or protection coils are not a part of the scope of delivery (see ‘Accessories / Miscel- laneous’ section).

Sensor material: Capillary length:

Ambient temperature: Max. sensor temperature: Permissible atmospheric humidity:

−20 to +55 °C

top scale value +15%

Max. 95% rel. humidity, non-condensing

Operating voltage:

none

Max. switching current: Min. switching current: Max. switching voltage: Min. switching voltage: Switching element: Switching contact: Electrical connection: Mounting / attachment:

15 (8) A 150 mA

230 V AC, 50 Hz 24 VAC, 50 Hz

microswitch

toggler, potential-free screw-type terminals

wall mounting

Protection rating: Protection class: Safety and EMC:

IP65

I

according to DIN EN 60730

Sensor:

liquid-filled capillary

General features:

scale: degrees Celsius, mechanical range restriction when external setting is used

TYPE

ITEM NO.

CONTROL RANGE

HYSTERESIS ADJUSTABLE (APPROX.)

SENSOR AXL FEATURES

EURO / PG

JET-110X

JA040100

−35 to +30 °C 2 – 20 K

9.6x122 mm

external setting / TR*

154.10 / II

JET-110XF

JA040200

−35 to +30 °C 2 – 20 K

9.6x122 mm

internal setting / TW*

155.20 / II

JET-120X

JA041100

0 to 60 °C 2 – 20 K

9.6x122 mm

external setting / TR*

154.70 / II

JET-120XG

JA041101

0 to 60 °C 2 – 20 K

9.6x122 mm

external setting / TR*

176.20 / II

JET-120XF

JA041200

0 to 60 °C 2 – 20 K

9.6x122 mm

internal setting / TW*

154.70 / II

JET-130X

JA042100

40 to 100 °C 2 – 20 K

9.6x122 mm

external setting / TR*

154.90 / II

JET-130XG

JA042101

40 to 100 °C 2 – 20 K

9.6x122 mm

external setting / TR*

179.20 / II

JET-130XF

JA042200

40 to 100 °C 2 – 20 K

9.6x122 mm

internal setting / TW*

155.50 / II

JET-133X

JA042300

40 to 100 °C

9.6x122 mm

external setting / TB**

160.30 / II

JET-133XF

JA042400

40 to 100 °C

9.6x122 mm

internal setting / TB**

161.30 / II

JET-140X

JA043100

70 to 130 °C 2 – 20 K

9.6x122 mm

external setting / TR*

158.60 / II

JET-140XF

JA043200

70 to 130 °C 2 – 20 K

9.6x122 mm

internal setting / TW*

159.20 / II

JET-143XF

JA043400

70 to 130 °C

9.6x122 mm

internal setting / TB**

165.10 / II

JET-150

JA044100

100 to 280 °C 8 – 50 K

6x80 mm

external setting / TR*

154.60 / II

JET-150F

JA044200

100 to 280 °C 8 – 50 K

6x80 mm

internal setting / TW*

155.20 / II

JET-153

JA044300

100 to 280 °C

6x80 mm

external setting / TB**

160.30 / II

JET-153F

JA044400

100 to 280 °C

6x80 mm

internal setting / TB**

161.40 / II

TR = temperature controller, TW = temperature monitor, TB = temperature limiter

* Control function heating or cooling ** Control function heating or cooling, locks when temperature rises, manual reset after temperature fall of at least 8 K

ACCESSORIES

Immersion sleeves for types with ‘X’ in the type specification: TH / NTH-140 see Seite 248 Immersion sleeves for types without ‘X’ in the type specification: TH / NTH-100 / 200 / 280 see Seite 248 Protection coil for all types: SW-200-12 see Seite 246

194

Catalogue 2023

Made with FlippingBook Annual report maker