PRODUCT CATALOGUE 2023 | alre.de

PLANT ENGINEERING

MULTI-STAGE CAPILLARY THERMOSTAT JMT-206 X 2 STAGES

TECHNICAL DATA

APPLICATION

Housing colour:

grey (lower part similar to RAL 7016, upper part similar to RAL 7035)

Multi-stage control of the temperature of liquid or gaseous media, e.g., for activating two-stage burners or heating registers. The SW-200-12 protecting coil is to be used for temperature control of non-aggressive gases in ducts; for temperature control in non-aggressive fluids, use the TH immersion sleeve, and in aggressive fluids, the NTH immersion sleeve. Immersion sleeves or protection coils are not a part of the scope of delivery (see ‘Accessories / Miscel- laneous’ section).

Sensor material: Capillary length:

Cu

1.5 m

Ambient temperature: Max. sensor temperature: Permissible atmospheric humidity:

−15 to +55 °C

top scale value +15%

Max. 95% rel. humidity, non-condensing

Operating voltage:

none

Max. switching current: Min. switching current: Max. switching voltage: Min. switching voltage: Switching element: Switching contact: Control function: Hysteresis between the stages: Electrical connection: Mounting / attachment:

15 (8) A 150 mA

230 V AC, 50 Hz 24 VAC, 50 Hz

microswitch

2 x togglers, potential-free

2-stage heating, 2-stage cooling, heat- ing or cooling with neutral zone

approx. 1 – 7 K, adjustable

screw-type terminals

wall mounting

Protection rating: Protection class: Safety and EMC:

IP65

I

according to DIN EN 60730

Sensor:

liquid-filled capillary scale: degrees Celsius

General features:

TYPE

ITEM NO.

CONTROL RANGE

HYSTERESIS IN THE STAGE (AP- PROX.)

SENSOR AXL FEATURES

EURO / PG

JMT-206 X

E6060340

20 to 80 °C

1 K

9.6x122 mm

External setting, TR

214.90 / II

TR = Temperature controller

ACCESSORIES

Immersion sleeves TH-140 / NTH-140 (see Seite 248), protection coil SW-200-12 (see Seite 246)

ILLUSTRATIONS

JMT-2..

JMT-2..

196

Catalogue 2023