Housing colour:
grey (lower part similar to RAL 7016, upper part similar to RAL 7035)
Multi-stage control of the temperature of liquid or gaseous media, e.g., for activating two-stage burners or heating registers. The SW-200-12 protecting coil is to be used for temperature control of non-aggressive gases in ducts; for temperature control in non-aggressive fluids, use the TH immersion sleeve, and in aggressive fluids, the NTH immersion sleeve. Immersion sleeves or protection coils are not a part of the scope of delivery (see ‘Accessories / Miscel- laneous’ section).
Sensor material: Capillary length:
Cu
1.5 m
Ambient temperature: Max. sensor temperature: Permissible atmospheric humidity:
−15 to +55 °C
top scale value +15%
Max. 95% rel. humidity, non-condensing
Operating voltage:
none
Max. switching current: Min. switching current: Max. switching voltage: Min. switching voltage: Switching element: Switching contact: Control function: Hysteresis between the stages: Electrical connection: Mounting / attachment:
15 (8) A 150 mA
230 V AC, 50 Hz 24 VAC, 50 Hz
microswitch
2 x togglers, potential-free
2-stage heating, 2-stage cooling, heat- ing or cooling with neutral zone
approx. 1 – 7 K, adjustable
screw-type terminals
wall mounting
Protection rating: Protection class: Safety and EMC:
IP65
I
according to DIN EN 60730
Sensor:
liquid-filled capillary scale: degrees Celsius
General features:
TYPE
ITEM NO.
CONTROL RANGE
HYSTERESIS IN THE STAGE (AP- PROX.)
SENSOR AXL FEATURES
EURO / PG
JMT-206 X
E6060340
20 to 80 °C
1 K
9.6x122 mm
External setting, TR
214.90 / II
TR = Temperature controller
ACCESSORIES
Immersion sleeves TH-140 / NTH-140 (see Seite 248), protection coil SW-200-12 (see Seite 246)