PRODUCT CATALOGUE 2023 | alre.de

PLANT ENGINEERING

DIFFERENTIAL PRESSURE SWITCH JDW-3 … -10 / JDL-111 … -116

TECHNICAL DATA

APPLICATION

Housing colour:

black

Monitoring of overpressure, differential or under-pressure of air and incombus- tible, non-aggressive gases. Exhaust or fan monitoring or flow monitor for securing electrical heat registers, as filter monitoring, air pressure shortage safeguard, limit value controller. JDW- …: Supplied without mounting bracket; can be screwed on directly (with 2 screws).

Ambient temperature: Permissible atmospheric humidity:

−15 to +80 °C

Max. 95% rel. humidity, non-condensing

Max. sensor temperature: permissible Medium tempera- ture:

80 °C

JDW-3

−15 to +80 °C

Operating voltage:

none 1 mA

Min. switching current: Max. switching voltage: Min. switching voltage: Switching element: Switching contact: Control function: Pressure connection: Mounting / attachment: Electrical connection:

230 VAC / 50 Hz, 24 VDC 12 VAC / 50 Hz, 12 VDC

JDW-...Z: Supplied with attached mounting bracket JZ-10

microswitch

JDL-111

toggler, gold contact, potential-free

JDL …: Supplied with attached mount- ing bracket JZ-10

switches if the pressure is undershot or exceeded

6.2 mm

Note: Once the differential pressure switch has connected a voltage > 24 V and a current > 0.1 A, the gold layer at the contacts will have burnt away. Thereafter, the differential pressure switch can only be operated at this or a higher power. Note: The hose set is not a part of the delivery scope and must be ordered separately.

wall mounting

screw-type terminals

Protection class: Protection rating: Safety and EMC:

II

IP54

JDL-112

according to DIN EN 60730

Sensor:

pressure membrane

Function type:

monitor (JDL-116 A controller)

CONVERSION TABLE PRESSURE Pa

kPa

bar

mbar

mmWs

1 Pa

= = = =

1

0.001

0.00001

0.01

0.101971 101.971 10197.1 10.1971

1 kPa 1 bar

1,000

1

0.01

10

100,000

100 0.1

1

1,000

1 mbar

100

0.001

1

1 mmWs =

9.80665

0.00980665

0.0000980665

0.0980665

1

TYPE ITEM NO. CONTROL RANGE

MAX. PRESSURE

HYSTERESIS (depen- dent on setting range)

FEATURES

EURO / PG

JDW-3

H531002 20 – 330 Pa

5,000 Pa

approx. 8 – 20 Pa

Max. switching current: 1.5 (0.4) AAC, 1 (0.2) ADC internal setting Max. switching current: 1.5 (0.4) AAC, 1 (0.2) ADC internal setting, fixing bracket Max. switching current: 1.5 (0.4) AAC, 1 (0.2) ADC internal setting Max. switching current: 1.5 (0.4) AAC, 1 (0.2) ADC internal setting, fixing bracket Max. switching current: 1.5 (0.4) AAC, 1 (0.2) ADC internal setting Max. switching current: 5 (1) AAC, 1 (0.2) ADC internal setting, silicone-free Max. switching current: 5 (1) AAC, 1 (0.2) ADC internal setting, silicone-free Max. switching current: 5 (1) AAC, 1 (0.2) ADC internal setting, silicone-free Max. switching current: 5 (1) AAC, 1 (0.2) ADC internal setting, silicone-free Max. switching current: 5 (1) AAC, 1 (0.2) ADC external setting, silicone-free

51.70 / II

JDW-3 Z

H531001 20 – 330 Pa

5,000 Pa

approx. 8 – 20 Pa

57.30 / II

JDW-5

H530996 30 – 500 Pa

5,000 Pa

approx. 10 – 25 Pa

51.70 / II

JDW-5 Z

H531000 30 – 500 Pa

5,000 Pa

approx. 10 – 25 Pa

57.30 / II

JDW-10

H530997 400 – 1600 Pa

5,000 Pa

approx. 30 – 60 Pa

51.70 / II

JDL-111

H5309098 20 – 300 Pa

15,000 Pa

approx. 10 – 15 Pa

57.80 / II

JDL-112

H5309100 40 – 600 Pa

30,000 Pa

approx. 22 – 33 Pa

56.60 / II

JDL-115

H5309136 100 – 1,000 Pa

30,000 Pa

approx. 20 – 40 Pa

56.60 / II

JDL-116

H530960

250 – 5,000 Pa

30,000 Pa

approx. 60 – 150 Pa

56.60 / II

JDL-116 A

H530978

250 – 5,000 Pa

30,000 Pa

approx. 60 – 150 Pa

64.10 / II

218

Catalogue 2023

Made with FlippingBook Annual report maker