HEATING TECHNOLOGY
ROOM TEMPERATURE CONTROLLER, MECHANICAL, RTBSB SURFACE-MOUNTED INSTALLATION – DESIGN BERLIN 2000
TECHNICAL DATA
APPLICATION
Design:
Berlin 2000
Control or monitoring of temperatures in closed spaces. Suitable for all heating systems. Valve actuator: normally closed. If nor - mally open heating valves are available, they should be connected with the cooling output of the changeover switch (toggler). Up to a maximum of 10 actuators for valves can be connected (normally closed, NC); with a toggler, on the NO contact, up to 5 units (in this context, please check the switching capacity listed in the technical specifications). Installation note: Owing to the existing wiring space in the controller itself, installation on a flush-mounted socket is recommended, but it can also be performed on a plane, non-conducting substrate. Explanations of technical terms can be found in the annex to the product catalogue or at www.alre.de.
Surface finish: Housing colour: Housing material:
matt
pure white, similar to RAL 9010
ABS plastic
Storage temperature: Permissible atmospheric humidity: Electrical connection:
−20 to +70 °C
Max. 95% rel. humidity, non-condensing
screw-type terminals 0.12 mm² – 2.5 mm²
Mounting / attachment:
Surface / wall mounting (4-hole assembly on flush-mounted socket)
Protection rating: Safety and EMC:
IP30
according to DIN EN 60730
Average power consumption:
< 0.5 W
Switching element:
bimetallic contact
Sensor:
bimetal
General features:
thermal feedback
TYPE / IMAGE
ITEM NO.
FEATURES
CIRCUIT DIAGRAM
EURO / PG
RTBSB-001.000
General features: Mechanical range limitation; scale: degrees Celsius ; external setting
MA010000
36.50 / I
Operating voltage: 230 VAC, 50 Hz Ambient temperature: 0 to 30 °C Protection class: II, if properly mounted Max. switching current: 10 (4) A
Max. switching voltage: 230 VAC, 50 Hz Min. switching voltage: 230 VAC, 50 Hz Switching power: 2300 W Switching contact: NC contact (max. 10 actuators) Output signal: switching (230 VAC, 50 Hz) Control function: heating Control range: 5 to 30 °C Hysteresis: approx. 0.5 K at a temperature change of max. 4 K / h General features: ECO function; mechanical range limitation; scale: degrees Celsius; external setting Operating voltage: 230 VAC, 50 Hz Ambient temperature: 0 to 30 °C Protection class: II, if properly mounted Max. switching current: 10 (4) A Max. switching voltage: 230 VAC, 50 Hz Min. switching voltage: 230 VAC, 50 Hz Switching power: 2300 W Switching contact: NC contact (max. 10 actuators) Output signal: switching (230 VAC, 50 Hz) Control function: heating Control range: 5 to 30 °C Hysteresis: approx. 0.5 K at a temperature change of max. 4 K / h Input ‘temperature reduction’: approx. 4 K (230 VAC, 50 Hz)
RTBSB-001.002
MA010100
38.80 / I
58
Catalogue 2023
Made with FlippingBook Annual report maker