HEATING TECHNOLOGY
ROOM TEMPERATURE CONTROLLER, MECHANICAL, FTR FLUSH-MOUNTED INSTALLATION – DESIGN BERLIN UP
TECHNICAL DATA
APPLICATION
Design:
Berlin UP PC plastic 0 to 30 °C
Control or monitoring of temperatures in closed, dry spaces. Suitable for all heating systems. Valve actuator: normally closed. If normally open heating valves are avail- able, they should be connected to the cooling output of the changeover switch (toggler), e.g., FTR 101.010. Up to a maximum of ten actuators for valves can be connected (normally closed, NC); with a toggler, on the NO contact, up to five units. In terms of visual aesthetics, the basic controllers, in combination with a 55x55 mm cover set, fit perfectly in many switch ranges without an insert frame. The basic controllers, in combination with a 50x50 mm cover set, fit in nearly all switch ranges with the use of an insert frame. Other complete devices (#21 types) with alre frame ‘Berlin’ (neutral), 50x50 mm cover (pure white, similar to RAL 9010, glossy) upon request.
Housing material:
Ambient temperature: Storage temperature: Permissible atmospheric humidity: Electrical connection: Mounting / attachment:
−20 to +70 °C
max. 95% rel. humidity, non-condensing
screw-type terminals
in flush-mounted socket – with cover set 50x50 mm or 55x55 mm, can be used with almost all switch ranges (deep flush-mounted socket recommended)
Protection rating: Protection class:
IP30
II, if properly mounted; with 24 VAC, protection class III
Safety and EMC:
according to DIN EN 60730
Max. power consumption:
< 0.5 W
Switching element:
bimetallic contact
Output signal:
switching
Sensor:
bimetal
Control range: Setting range:
5 to 30 °C 5 to 30 °C
Hysteresis:
approx. 0.5 K at a temperature change of max. 4 K / h
General features:
thermal feedback; multi-digit display * … 6
TYPE / IMAGE
ITEM NO.
FEATURES
CIRCUIT DIAGRAM EURO / PG
FTR 101.000#00
General features: mechanical range limitation; external setting; protective cap; contact hazard protection cover plate; VDE-tested
UA010017
56.80 / I
Operating voltage: 230 VAC, 50 Hz Max. switching current: 10 (4) A
Max. switching voltage: 230 VAC, 50 Hz Min. switching voltage: 230 VAC, 50 Hz Switching power: 2300 W Switching contact: NC contact (max. 10 actuators) Control function: heating Cover sets are offered in various designs (see the separate overview, ‘alre flush-mounted range (cover sets)’) and are not included in the delivery. Suitable set no: JZ-001.xxx, for example: 50x50 mm cover set, pure white, glossy: JZ-001.000 55x55 mm cover set, pure white, glossy: JZ-001.100 BUSCH-JAEGER cover set Reflex SI / SI Linear, pure white, glossy: JZ-001.200 / BJ future linear, solo, axcent, carat, studio white (RAL 9016), glossy; JZ-001.320 / BJ
FTR 101.000#21
UN010009 Similar to FTR 101.000#00, but with scope of delivery: controller, alre frame ‘Berlin’ (neutral), 50x50 mm cover, pure white (similar to RAL 9010), glossy
71.90 / I
94