Dacta Therm PPR Piping System

Linear expansion

The linear expansion of pipes bases on the difference between the operating temperature and the installation temperature.

The coefficient (a) of linear expansion of Dacta Therm - Fiberglass Reinforced PP-R pipes is α Dacta Therm - Fiber glass Reinforced PP-R Pipe: 0.035 mm/mK The Dacta Therm - Fiberglass Reinforced PP-R pipes require enough space to expand (see page 7). An expansion control is necessary for straight and long fiberglass pipes (over 120 ft). The Dacta Therm PP-R pipes without the sta- bilizing compound should have expansion control on every 30 ft of straight runs.Risers made of - composite pipes may be installed tightly without expansion compensation. The following for-mula, data tables, calculation examples and diagrams help to determine the linear expansion. The difference between working temperature and maximum or minimum installa-tion temperature is fundamental to calculate the linear ex-pansion. ∆L=LDt* a ∆L=Linear Expansion (mm) L =Pipe Length (m) ∆T=Temperature Difference between Working and Installation temperature (° K, °C or °F) a = Coefficient of Linear Expansion (mm/mK) Example; if a 2m long Dacta Therm - fiberglass re-inforced PP-R pipe operates in 65 °C and is installed in 25° C, the linear expansion will be calculated as follows; ∆L=L*∆t* α ∆L=2*40*0,035 ∆L=2,8 mm

The linear expansion of pipes is based on the difference be- tween the operating temperature and the installation tem- perature:

T = T operating temperature - T installation temperature

For this reason cold water pipes have practically no linear expansion. Due to the heat-dependent expansion of the material, the linear expansion must be given special consideration for hot water and heating installations. There is a difference between the installation types: • Open installation • Installation in ducts • Concealed installations with piping insulated In the case of exposed installation pipes (e.g. in the base- ment), perfect visual characteristics and dimensional sta-bility are significant. Dacta Therm PP-R pipes for hot water and heating systems facilitate this. The coefficient (a) of linear expansion of Dacta Therm PP-R pipes is comparable to the linear expansion of metal pipes: The coefficient of linear expansion of Dacta Therm PP-R standard piping systems without stabilizing compo-nents is α Dacta Therm Standard PP-R Pipe: 0.150 mm/mK

Pipe Length (mt) Difference in temperatures (°C) ΔT = T operating temperature - T installation temperature 10°C 20°C 30°C 40°C 50°C 60°C 70°C 80°C 10°C 20°C 30°C 40°C 50°C 60°C 70°C 80°C 10°C 20°C 30°C 40°C 50°C 60°C 70°C 80°C 1,0 1.50 3.00 4.50 6.00 7.50 9.00 10.50 12.00 0.40 0.70 1.10 1.40 1.80 2.10 2.50 2.80 0.30 0.60 0.90 1.20 1.50 1.80 2.10 2.40 2,0 3.00 6.00 9.00 12.00 15.00 18.00 21.00 24.00 0.70 1.40 2.10 2.80 3.50 4.20 4.90 5.60 0.60 1.20 1.80 2.40 3.00 3.60 4.20 4.80 3,0 4.50 9.00 13.50 18.00 22.50 27.00 21.50 36.00 1.10 2.10 3.20 4.20 5.30 6.30 7.40 8.40 0.90 1.80 2.70 3.60 4.50 5.40 6.30 7.20 4,0 6.00 12.00 18.00 24.00 30.00 36.00 42.00 48.00 1.40 2.80 4.20 5.60 7.00 8.40 9.80 11.20 1.20 2.40 3.60 4.80 6.00 7.20 8.40 9.60 5,0 7.00 15.00 22.50 30.00 37.50 45.00 52.50 60.00 1.80 3.50 5.30 7.00 8.80 10.50 12.30 14.00 1.50 3.00 4.50 6.00 7.50 9.00 10.50 12.00 6,0 9.00 18.00 27.00 36.00 45.00 54.00 63.00 72.00 2.10 4.20 6.30 8.40 10.50 12.60 14.70 16.80 1.80 3.60 5.40 7.20 9.00 10.80 12.60 14.40 7,0 10.50 21.00 31.50 42.00 52.50 63.00 73.50 84.00 2.50 4.90 7.40 9.80 12.30 14.70 17.20 19.60 2.10 4.20 6.30 8.40 10.50 12.60 14.70 16.80 8,0 12.50 24.00 36.00 48.00 60.00 72.00 84.00 96.00 2.80 5.60 8.40 11.20 14.00 16.80 19.60 22.40 2.40 4.80 7.20 9.60 12.00 14.40 16.80 19.20 9,0 13.50 27.00 40.50 54.00 67.50 81.00 94.50 108.00 3.20 6.30 9.50 12.60 15.80 18.90 22.10 25.20 2.70 5.40 8.10 10.80 13.50 16.20 18.90 21.60 10,0 13.50 27.00 40.50 54.00 67.50 81.00 94.50 108.00 0.00 9.00 12.00 15.50 18.00 21.00 24.00 Difference in temperatures (°C) ΔT = T operating temperature - T installation temperature Difference in temperatures (°C) ΔT = T operating temperature - T installation temperature

Table 7

Linear expansion of Dacta Therm Solid PP-R pipes Linear expansion ∆L (in): Dacta Therm Standard PP-R Pipe = α - 0.150 mm/mK

Linear expansion of Dacta Therm- fiberglass reinforced PP-R pipes Linear expansion DL (in): Dacta Therm - Fiberglass Reinforced PP-R Pipe = α - 0.035 mm/mK

The linear expansion is calculated according to the following formula: ∆L = Lo x α x ∆T ∆L : Amount of elongation α

: Linear expansion coefficient

Lo ∆T

: First length

: Difference in temperatures

33

Made with FlippingBook Annual report