Branch Panel:

MAIN PANEL CALCS

ELECTRICAL NOTES

Location: LIVING ROOM 01

Volts: 120/240 Single

Mains Type: A.I.C. Rating:

Supply From:

Wires: 3 Phases: 1

Tuscon,AZ, USA 888-864-0184 inquire@frameupnow.com www.frameupnow.com

1.

THIS DRAWING DEPICTS THE ELECTRICAL SYSTEM FOR THE Immense_550_Stan_Huff. IT PROVIDES A VISUAL REPRESENTATION OF THE ELECTRICAL LAYOUT AND COMPONENTS, INCLUDING POWER DISTRIBUTION, LIGHTING, AND CONTROL SYSTEMS. THE ELECTRICAL SYSTEM IS DESIGNED TO MEET THE SPECIFIC REQUIREMENTS OF THE BUILDING, INCLUDING POWER DISTRIBUTION, LIGHTING, AND SPECIALIZED ELECTRICAL EQUIPMENT NEEDS, AS PER THE PROJECT SPECIFICATIONS AND APPLICABLE CODES AND STANDARDS. THE ELECTRICAL SYSTEM INSTALLATION SHALL COMPLY WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC), INTERNATIONAL BUILDING CODE (IBC), AND ALL OTHER APPLICABLE LOCAL, STATE, AND NATIONAL CODES AND REGULATIONS. LOCATIONS AS NEEDED, DEVICES ARE SHOWN ON PLANS IN APPROXIMATE IDEAL LOCATIONS, UNLESS SPECIFICALLY DIMMENSIONED. OPEN WALLS AS NEEDED TO ALLOW FOR NEW ELECTRICAL INSTALLATIONS. LABEL ALL CIRCUITS ON JUNCTION BOXES, RECEPTACLES,DATA, SMOKE DETECTOR, AND EQUIPMENT IN PANEL BOX. INSTALL RACEWAY AS NEEDED FOR DDC, ACCESS CONTROL, LOW VOLTAGE WIRING & DATA. RELABEL POWER, DATA & FIRE ALARM FOR ROOM #CHANGES. VERIFY ALL CIRCUITS LABELED ON PRINT ARE CORRECT BEFORE WORKING ON THEM. NOTE ON SITE PLAN – ALL CHANGES OR MISSING DETAIL TO BE INCORPORATED INTO THE MASTER PLAN. DRAWINGS ARE DIAGRAMMATIC ONLY FOR THE PURPOSE OF SHOWING FIXTURE AND OUTLET LOCATIONS. ELECTRICAL CONTRACTOR TO VERIFY SERVICE SIZE BY CALCULATION BASED UPON ACTUAL NAME PLATE RATINGS OF SELECTED EQUIPMENT. VERIFY LOCATION OF SERVICE ENTRANCE WITH POWER COMPANY. PROVIDE UFER GROUND IN BUILDING FOUNDATION AT SERVICE ENTRANCE LOCATION. PROVIDE A MIN. OF 20 FEET OF ONE *4 BARE COPPER UFER WIRE EMBEDDED IN CONCRETE FOOTING AT THE SERVICE ENTRANCE LOCATION WHERE APPROVED BY LOCAL SERVICE PROVIDER. PROVIDE WATERPROOF FIXTURES IN ALL HIGH MOISTURE AREAS (EXTERIOR, SHOWER AND TUB CEILINGS ETC.) PROVIDE DEDICATED CIRCUITS TO EACH BATH, DEN, FAMILY ROOM, BEDROOM, LOFT, KITCHEN REFRIGERATOR, KITCHEN FREEZER DISHWASHER, AND ANY AREA/ITEM SPECIFIED BY OWNER. INCANDESCENT FIXTURES WITH OPEN OR PARTIALLY ENCLOSED LAMPS, PENDANT FIXTURES, AND LAMP HOLDERS ARE NOT PERMITTED IN CLOSETS. ALL WORKMANSHIP AND MATERIALS TO CONFORM WITH THE 2015 IRC. PROVIDE A MIN. OF 20 FEET OF ONE *4 BARE COPPER UFER WIRE EMBEDDED IN CONCRETE FOOTING AT THE SERVICE ENTRANCE LOCATION WHERE APPROVED BY LOCAL SERVICE PROVIDER. PROVIDE A BONDING CONDUCTOR CONSISTING OF A MINIMUM OF ONE *4 BARE COPPER WIRE CONNECTING THE BUILDING'S METAL WATER PIPING SYSTEM TO THE SERVICE EQUIPMENT ENCLOSURE GROUNDING.

ELECTRICAL CALCS LIGHT AND OUTLETS 1141 @ 3W 3423 W 3 APPLIANCE CIRCUITS 4500 W DRYER 5000 W WASHER 1500 W WATER HEATER 5000 W REFRIG. 1500 W DISPOSAL 1500 W

Enclosure: Type 1 Mounting: Recessed

MCB Rating: 1 A Mains Rating: 200 A

2.

Notes:

3.

Circuit Numb er Circuit Description

Circuit Numb er

Length Wire Size

Wire Size Length

Number of Elements Rating

Number of Elements Circuit Description

AA, Ethiopia Info@housedocs.store www.housedocs.store

A

B

Rating

4. 5. 6. 7. 8. 9.

2-#10, 1-#10, 1-#10 1-#12, 1-#12, 1-#12 1-#10, 1-#10, 1-#10 1-#12, 1-#12, 1-#12 1-#12, 1-#12, 1-#12 1-#12, 1-#12, 1-#12 1-#12, 1-#12, 1-#12 1-#12, 1-#12, 1-#12

1-#10, 1-#10, 1-#10 1-#12, 1-#12, 1-#12

KITCHEN LIGHTING

BEDROOM 2&3 LIGHTING

1

9

20 A 41' - 0 19/32"

533 VA 812 VA

48' - 4 1/16"

20 A

18

2

BEDROOM 2&3 RECEPTACLE

3 OUTDOOR GFCI

3

20 A 56' - 4 1/8"

540 VA 1620 VA

57' - 8 5/32"

20 A

9

4

KEY PLAN

2500 VA

2-#8, 1-#8, 1-#10

5 REFRIGRATOR

1

20 A 33' - 0 5/32"

1500 VA

13' - 8 5/8"

50 A

1 RANGE

6

10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20.

TOTAL

22,423W

7 BATH 1 GFCI

4

20 A 44' - 8 17/32"

291 VA 2500 VA --

--

--

--

--

8

2-#10, 1-#10, 1-#10

2500 VA

9 BATH 2 GFCI

5

20 A 54' - 11 7/32"

291 VA

43' - 2 1/8"

30 A

1 WATER HEATER 10

FRIST 10,000 @ 100% REMAINDER @ 40% MINI. SPLIT UNITS

10,000 W 4969W 10,000 W

11 DISHWASHER

1

30 A 18' - 9 11/32"

1500 VA 2500 VA --

--

--

--

--

12

1-#12, 1-#12, 1-#12 1-#14, 1-#14, 1-#14 1-#14, 1-#14, 1-#14 1-#12, 1-#12, 1-#12 1-#12, 1-#12, 1-#12 1-#12, 1-#12, 1-#12

BEDROOM 1RECEPTACLE

13 OVENHOOD

1

20 A 11' - 2 15/16"

180 VA 900 VA

52' - 11 3/4"

20 A

5

14

TOTAL

24,969 W

NO.

DESCRIPTION

DATE

WASHING MASHINE

15 DRYER

1

30 A 37' - 9 13/16"

2500 VA 1500 VA

34' - 11 29/32"

20 A

1

16

24,969 W DIVIDED BY 240V = 104 AMPS TOTAL

1080 VA

17 --

--

--

--

--

2500 VA

38' - 8 17/32"

20 A

6 RECEPTACLE

18

(USE 200 AMP SERVICE)

2-#6, 1-#6, 1-#10

19 CONDENSER

1

60 A 50' - 6 21/32"

2500 VA 180 VA

38' - 10 11/16"

15 A

4 HALL LIGHTING 20

21 --

--

--

--

--

2500 VA 496 VA

48' - 1 7/16"

15 A

8 BED 1 LIGHTING 22

1-#12, 1-#12, 1-#12 1-#14, 1-#14, 1-#14

LIVING ROOM LIGHTING

Lighting - Dwelling Unit

23

7

15 A 49' - 9 15/32"

139 VA 300 VA

37' - 6 3/4"

20 A

5

24

NOTE:

25 KITCHEN GFCI

5

20 A 30' - 10 29/32"

900 VA

26

ELECTRICAL ABBREVIATIONS LIST

16684 VA

16042 VA

139 A

134 A

Legend:

1P A AC ACLG ADO AF

1 POLE (2P, 3P, 4P, ETC.) AMPERE ABOVE COUNTER OR AIR CONDITIONER ABOVE CEILING AUTOMATIC DOOR OPENER AMP FRAME ABOVE FINISHED FLOOR ABOVE FINISHED GRADE ARC FAULT CIRCUIT INTERRUPTER AIR HANDLING UNIT ALUMINUM ALTERNATE AMPERE AMPLIFIER ANNUNCIATOR APPROX APPROXIMATELY AQUASTAT ARCHITECT, ARCHITECTURAL AMP SWITCH AMP TRIP AUTOMATIC TRANSFER SWITCH AUTOMATIC AUXILIARY AUDIO VISUAL AMERICAN WIRE GAUGE BATTERY BOARD BUILDING BUILDING MANAGEMENT SYSTEM

CTR CU DCP DEPT DET DIA DISC DIST DN DPR DS DT DWG DDC EC ELEC ELEV EM EMS EMT EP EQUIP EWC EXIST

CENTER COPPER DOMESTIC WATER CIRCULATING PUMP DEPARTMENT DETAIL DIAMETER DISCONNECT DISTRIBUTION DOWN DAMPER SAFETY DISCONNECT SWITCH DOUBLE THROW DRAWING DIRECT DIGITAL CONTROL ELECTRICAL CONTRACTOR ELECTRIC, ELECTRICAL ELEVATOR EMERGENCY ENERGY MANAGEMENT SYSTEM ELECTRICAL METALLIC TUBING ELECTRIC PNEUMATIC EQUIPMENT ELECTRIC WATER COOLER EXISTING EXHAUST EXPLOSION PROOF FIRE ALARM FIRE ALARM BOOSTER POWER SUPPLY PANEL FIRE ALARM CONTROL PANEL FAN COIL UNIT FIXTURE FLOOR FLUORESCENT FUSE FUSED SAFETY DISCONNECT SWITCH GAUGE GALLON GALVANIZED GENERAL CONTRACTOR GENERATOR GROUND FAULT CIRCUIT INTERRUPTER GROUND FAULT PROTECTOR GROUND GALVANIZED RIGID STEEL (CONDUIT) GYPSUM BOARD

HT HTG HTR HV HVAC CONDITIONING HWP

HEIGHT HEATING HEATER HIGH VOLTAGE HEATING, VENTILATING AND AIR CONDITIONING HYDRONIC WATER PUMP INTERRUPTING CAPACITY ISOLATED GROUND INTERMEDIATE METAL CONDUIT INCANDESCENT INFRARED INTERLOCK WITH JUNCTION BOX KILOVOLT KILOVOLT-AMPERE KILOVOLT-AMPERE REACTIVE KILOWATT KILOWATT HOUR LOCATE OR LOCATION LIGHT LIGHTING LIGHTNING LOW VOLTAGE MAXIMUM MAGNETIC STARTER MOMENTARY CONTACT MECHANICAL CONTRACTOR MAIN CIRCUIT BREAKER MOTOR CONTROL CENTER MAIN DISTRIBUTION CENTER MAIN DISTRIBUTION PANEL MANUFACTURERMAIN FUSED DISCONNECT SWITCH MANHOLE MICROPHONE MINIMUM MANUAL MOTOR STARTER MULTIOUTLET ASSEMBLY MOTOR STARTER PANELBOARD MAIN SWITCHBOARD MOUNT EMPTY CONDUIT UNDERWRITERS LABORATORIES MISCELLANEOUS MAIN LUGS ONLY

Load Classification

Connected Load

Demand Factor

Estimated Demand

Panel Totals

1500 VA 5000 VA 5000 VA 5000 VA 5000 VA 400 VA 8580 VA 1360 VA 950 VA

100.00% 100.00% 80.00% 100.00% 100.00% 100.00% 100.00% 100.00% 100.00%

1500 VA 5000 VA 4000 VA 5000 VA 5000 VA 400 VA 8580 VA 1360 VA 950 VA

Lighting - Dwelling Unit

Total Est. Demand: 31725 VA Total Conn. Load: 32725 VA

Other

LEGEND:

Receptacle

Total Conn.: 136 A

Lighting

Total Est. Demand: 132 A

CONDENSER

AFF AFG AFI AHU AL ALT AMP AMPL ANNUN AQ-STAT ARCH

WATER HEATER

IC IG IMC INCAND IR I/W J-BOX KV KVA KVAR KW KWH LOC LT LTG LTNG LV MAX MAG.S M/C MC

DRYER RANGE

Notes: REFRIGERATOR

AS AT ATS AUTO AUX AV AWG BATT BD BLDG BMS C CAB CAT CATV CB CCTV

PROJECT

IMMENSE-550

EXH EXP FA FABP SUPPLY PANEL FACP

CONDUIT CABINET CATALOG

MCB MCC MDC MDP MFR MH MIC MIN MISC MLO MMS MOA MSP MSBD MT MT.C UL

FCU FIXT FLR FLUOR FU FUDS GA GAL GALV GC GEN GFI GFP GND GRS GYP BD

CABLE TELEVISION CIRCUIT BREAKER CLOSED CIRCUIT TELEVISION

DRAWING NAME

SCHEDULE

CKT CLG

CIRCUIT CEILING

COMB CMPR CONN CONST CONT CONTR CONV CP CRT CT

COMBINATION COMPRESSOR CONNECTION CONSTRUCTION CONTINUATION OR CONTINUOUS CONTRACTOR CONVECTOR CIRCULATING PUMP CATHODE-RAY TUBE CURRENT TRANSFORMER

Owner 0426_15

DATE: PROJECT NUMBER: DESIGNED BY: CLIENT NAME:

8/5/2025 11:28:50 AM

Designer

housedocs.store

CHECKED BY: DRAWN BY:

Checker

E101

SCALE:

1/4" = 1'-0"