Phase Electrical General Catalogue

SWITCHGEAR, DISTRIBUTION & CONTROL Switch Disconnectors

Glasgow Fuse-Switch-Disconnectors & Switch-Disconnectors

Glasgow Fuse-Switch-Disconnector

• Units are fitted with HRC Fuselinks of maximum rating but will accept fuselinks of a lower rating. • SPSN and TPSN indicate switched neutral. • Neutral makes first and breaks last.

Part No. Poles Nominal Unit Rating, Ie (A) 61GNC SPSN 63

Eaton 415V Fuse(s) Fitted

Suitable Fuselinks

Copper Switch Links Fitted

Motor Ratings AC23A Ue 415V kW HP

All units are supplied with fuselinks or switchlinks fitted. Glasgow fuse switch disconnectors and switch disconnectors meet the constructional requirements for isolation of and are type tested to BS EN 60947-3. Five frame sizes are available to provide a range from 63A to 800A, with utilisation category AC22A and AC23A Ue 415V ratings. All units have retractable operating handles which drive overcentre mechanisms incorporating powerful operating springs. Flag “on-off” indication is provided and terminal cover shields prevent contact with live metal. Surface-mounting enclosures comprise heavy gauge steel body plates incorporating cast iron frame members and are rustprotected, with a light grey paint finish (RAL7004). Front access doors, which are detachable, are fitted with dust-excluding gaskets and are interlocked to prevent opening when the switch is ‘on’.

63SB4 SB3 & SB4 63MLK 22

30

63GNC

TPN

64GC

TPSN 101GNC SPSN 100 100SD5 SB3, SB4, SO & SD5 103GNC TPN 104GC TPSN 151GNC SPSN 160 160SF6 SF3 & SF6 200MLK 90 153GNC TPN 154GC TPSN 201GNC SPSN 200 200SF6 SF3 & SF6 200MLK 90 203GNC TPN 204GC TPSN 303GNC TPN 315 315SF7 SF3 & SF7 400MLK 110 TPSN 403GNC TPN 400 400SF8 SF3 & SF8 400MLK 110 TPSN 503GNC TPN 500 500SH9 SH8 & SH9 630MLK 225 100MLK 22 304GC 404GC

30

125

Part No.

Nominal Unit

Nominal Rating, Ie AC21 (A)

Copper Switch Links Fitted

Motor Ratings AC23A Ue 415V kW HP

125

63GNL 103GNL

63

125 125

63MLK 100MLK

22 22

30 30

150

100

-

160 (Use 200A Switch-Disconnector)

-

-

-

-

150

203GNL

200

315

200MLK

90

125

300 300

-

315 (Use 400A Switch-Disconnector)

-

-

-

-

603GNC TPN 630 630SH9 604GC TPSN 803GNC TPN 800 800SH10 SH8 & SH10 -

630MLK 225

403GNL

400

630

400MLK 110

150

800MLK 300

400

-

500 (Use 630A Switch-Disconnector)

-

-

-

-

804GC

TPSN

* If DP fuse-switch-disconnectors are required, use SPSN and replace the supplied switch link with a compatible fuselink. Stud size: 63/100A = tunnel terminal, 160/200A = M10, 300/400 = M14, 500/800A = see page 148, “copper terminal plate”

603GNL 803GNL

630 800

1000 1000

400MLK 225 800MLK 300

300 400

Exel 2 Switch-Disconnectors & Switch-Disconnector Fuses

Part No. Poles Utilisation Category at Ue 415V to BS EN 60947-3

250V DC Rating to BS5419 DC23 (A)

Blank Endplate

AC22A (A) AC23A (A)

-

SPSN 20

11

20 1)

EP 842

15AXD2 DP 15AXTN2 TPN - DP 30AXTN2 TPN - DP 60AXTN2 TPN - 30AXD2 60AXD2

SPSN 32

22

32

-

Exel 2 switch disconnectors and switch-disconnector fuses meet the constructional requirements for isolation of and are type tested to BS EN 60947-3. Switches are of the quick make and break type, suitable for use on AC or DC. Units have removable moving contact assemblies to facilitate wiring. Exel 2 surface-mounting enclosures are fabricated from rust-protected sheet steel with a light grey paint finish. Removable blank top and bottom end plates (except for 20 and 32A top end plates which incorporate knockouts) and gasket doors give IP41 protection. Chromium-plated front operated handles, with “ON (I) OFF (O)” indication, and internal fixing enabling units to be mounted closely side by side. Interiors comprise porcelain bases fitted with non-ferrous conducting components.

SPSN 63

-

63

EP 539

39

SPSN 100

-

100

-

100AXD2 DP 100AXTN2 TPN 125AXTN2 TPN 125

52

52

-

-

SPSN indicates switched neutral. 1) 20A units are DC22.

138

Together we generate value

Made with FlippingBook - Online magazine maker