15-15 Selection Guide
Wireless IoT Sensing Devices: Wzzard™ Mesh Sensor Nodes – for Industrial Application Sensors
SKY Servers 3 2 Intelligent Systems 1 IIoT Software Solutions
BB-WSD2x industrial series
8 9 7 6 5 4
AI & Advanced Computer Vision
Intelligent HMI and Monitors
) BB- WSD2C21150 Industrial cooler, HVAC node
) BB- WSD2C06010 Industrial digital input node
) BB- WSD2C31010 Industrial power monitor node
) BB- WSD2M06010 Industrial digital input node
) BB- WSD2M31010 Industrial power monitor node
) BB- WSD2M3101P2K Industrial power monitor node
) BB- WSD2M3101R100
Model
Automation Computers
Industrial power monitor node
Description
Wireless Technology
Low power 802.15.4e, SmartMesh IP (to SmartSwarn 342 gateway) via MQTT protocol
Intelligent Transportation Platforms
Conduit (UL Type 3 outdoor approved) 12.7mm (0.5 in)
Conduit (UL Type 3 outdoor approved) 12.7mm (0.5 in) 2 AI, 1 DI, 1 DO, 2 Thermocouples, 2 Thermistors, internal temperature, antenna, cable
Conduit (UL Type 3 outdoor approved) 12.7mm (0.5 in)
M12
M12
M12
M12
Connector
Mission Critical CompactPCI Platforms
2 AI, Vbat measurement, 1 DI, internal temperature, Switched Vbat Power Out (2 sec.), antenna, cable
12 AI, Vref measurement, 1 DI, internal temperature, Switched 3.3V Power Out (100 ms), antenna, cable
6 DI, internal temperature, antenna, cable
3 AI, 1 DI, internal temperature, antenna, cable
6 DI, internal temperature, antenna, cable
3 AI, 1 DI, internal temperature, antenna, cable
Includes
13 15 14 16 12 11 10 Utility and Energy Solutions EtherCAT Solutions and Automation Controllers Industrial Communication Remote I/O, Wireless I/O & Sensors Intelligent Edge DAQ Devices Serial Communication Hgh Speed DAQ Solutions Intelligent Motion Control Solutions
External Antenna (included)
RP-SMA, Omni-directional, 3.8 dBi, 2.4 GHz
Internal Power: (2) 3.6V 2400 mAH Lithium Thionyl Chloride AA Batteries Battery Life: >5 years – based on 1 min. sensor sampling and reporting external input voltage: 10-30 V DC @ 40mA peak Switched Vbat: Battery Power – Turned on at time of measurement (20 mA max.) Switched Vref: 3.3V (± 0.1%) – Turned on at time of measurement (20 mA max.)
Power
Sensor Power Out
Analog Input (0 -10 VDC, 0 - 20 mA, 4 - 20 mA) Digital Input (0 - 48 V DC ) Digital Input Frequency 1-1K Hz (accuracy ± 1 Hz) Digital input counter integrated temperature Thermocouple (J, K, N, R, S, T, B, E) Digital output, sinking, up to 100mA @ 30V DC
Sensors
Device authentication, 128-bit, AES-based wncryption with multiple keys, message integrity check (MIC), synchronized key changeovers, customized key rotation
Wireless Security
-40 to +80 °C (operating)
Temperature
IP67 rated fiber reinforced polyester PBT
Enclosure Mounting Option Mounting Option
(4) Mounting ears, M5 (#10) screws (UL approved option)
Magnetic Mounting (via internal enclosure magnet) Pull Force 2.13 kg (4.7 lb) Note: Magnetic mounting models not rated for UL installations.
UL C1/D2, CE, FCC, EN62479 (lower power), shock, vibration Yes. Indoor / Outdoor, w/ mounting ear installation
UL C1/D2, CE, FCC, EN62479 (lower power), shock, vibration
UL C1/D2, CE, FCC, EN62479 (lower power), shock, vibration Yes. Indoor / Outdoor, w/ mounting ear installation
CE, FCC, EN62479 (lower power), shock, vibration
CE, FCC, EN62479 (lower power), shock, vibration
CE, FCC, EN62479 (lower power), shock, vibration
CE, FCC, EN62479 (lower power), shock, vibration
Certifications
UL Listed C1/D2 Conditions
No (M12 connector not UL)
No (M12 connector not UL)
No (M12 connector not UL)
No (M12 connector not UL)
(pending)
Made with FlippingBook - Online magazine maker