Watson McDaniel Steam Design Guide

Heat Exchanger Example: Heating Water with Steam using a Modulating Control Valve HEAT EXCHANGER FORMULAS & EXAMPLE

Now, what happens when the water flow rate thru the HX reduces to the point that the steam pressure goes into vacuum? This occurs at water flow rates below about 58 GPM down to the minimum of 25 GPM. Since the HX will be operating in vacuum, the condensate would not effectively drain regardless of the steam trap size chosen. This is why a vacuum breaker must be added to the top of the HX. The vacuum breaker draws in air to neutralize the pressure in the HX which allows the condensate to drain (see Figure 19).

Heat Exchanger System with Steam Trap shown with and without Vacuum Breaker

Figure 19:

System without Vacuum Breaker

System with Vacuum Breaker

100 psig

Sub-atmospheric pressure

100 psig

0 psig

OPEN Vacuum Breaker

- 5 psig

Condensate Backs Up into Heat Exchanger

1 psig

2.31 ft. water coulmn

Condensate will not flow without a vacuum breaker

Condensate flows through trap

2.31 Ft. X 0.433 = 1 psig

The HX can be properly drained using a steam trap as long as there is no BACK PRESSURE in the condensate return line. If there is back pressure in the condensate return line, a Pumping Trap must be used.

75

Tel: 610-495-5131 • Pottstown PA • USA •• www.watsonmcdaniel.com

Made with FlippingBook - Online magazine maker