Fluke 1770 Series Power Quality Analysers
Recommended Accessories
Voltage inputs Number of inputs
4 inputs, 3 phases and neutral referenced to PE (5 connectors)
Measurement category Maximum input voltage
1000 V CAT III / 600 V CAT IV
1000 V rms / 1000 V DC (1700 Vpk)
Wye and single phase: variable (50 V – 1000 V) Delta: Variable (100 V – 1000 V) IEC 61000-4-30 Class A compliance for the nominal voltages (V din ) 100 V – 690 V
i17XX-FLEX6KIP IP65 iFlex ® 6000 A 90 cm Current Probes (individual, 3pk or 4pk) See page 182
I400S AC Current Clamp See page 182
Nominal voltage range
Input impedance
10 MΩ between P-P and P-N, 5 MΩ between P-PE and N-PE DC to 30 kHz for PQ measurements, excluding transients
Bandwidth Resolution
24-bit synchronous sampling
Sampling frequency
80 kS/s at 50/60 Hz
Scaling
1:1, variable for use of potential transformers
i40s-EL/3pk 40 A Clamp-on Current Transformer (individual or 3pk) See page 182
80I-2010S/3PK 2000 A AC/DC Current Clamp (individual or 3pk) See page 183
Voltage transients Measurement range
±8 kV
1775: 1 MS/s 1777: 1 MS/s, 20 MS/s
Sampling rate
Bandwidth
DC to 1 MHz
Trigger
Adjustable trigger level. Triggers on high-frequency components >1.5 kHz
Resolution
14-bit synchronous sampling
Current inputs Number of inputs
Antenna Cable Antenna cable 5 m
177X WiFi/BLE Wi-Fi/BLE Module
4 inputs 3 phases and Neutral, range selected automatically to attached sensor
1 A to 1500 A with i17XX-FLEX1500 12 1 A to 1500 A with i17XX-FLEX1500 24 3 A to 3000 A with i17XX-FLEX3000 24 6 A to 6000 A with i17XX-FLEX6000 36 40 mA to 40 A with clamp i40s-EL 4 A to 400 A with clamp i400s-EL 20 A to 2000 A with 80i-2010-EL clamp
AC
Range
DC
Bandwidth Resolution
DC to 30 kHz
24-bit synchronous sampling
Included Accessories 17XX iFlex ® 1500 A 24 IN,
Sampling frequency
80 kS/s at 50/60 Hz
Scaling
1:1, variable
Voltage Test Lead 3-Phase+N, 4x AC285 Black Alligator Clips, 1x AC285 Green Alligator Clip, USB-C Cable, Line Cord, FLK- 17XX 0.18 M Test Lead Set, Green Test Lead, Cable Marker Set, WiFi/BLE Module (1775, 1777), Magnet Probe (1775, 1777), Hanger Kit (1775, 1777), Black Soft Case (1775), Hardcase (1777) Ordering Information FLUKE-1773 Three-Phase Power Quality Analyser w/ Accessories FLUKE- 1773/BASIC Three-Phase Power Quality Analyser Only FLUKE-1775 Three-Phase Power Quality Analyser w/ Accessories FLUKE- 1775/BASIC Three-Phase Power Quality Analyser Only FLUKE-1777 Three-Phase Power Quality Analyser w/ Accessories FLUKE- 1777/BASIC Three-Phase Power Quality Analyser Only
Clamp: 50 mV / 500 mV rms; CF 2.8 Rogowski Coil: 15 mV / 150 mV rms at 50 Hz, 18 mV / 180 mV rms at 60 Hz; CF 4 all at nominal probe range
Input voltage
Input impedance
11 kΩ
Aux inputs Wired connection with 17xx-AUX adapter Number of inputs
2
Input range
Direct: 0 V DC to ±10 V DC 0 V to 1000 V DC
Input impedance
Direct: 2.92 MΩ
C ontact your local distributor for price and availability. fluke.co/wtb
fluke.co/powerquality
Power Quality
105
Made with FlippingBook Learn more on our blog