10032026_CoHE _V5

Safety training

Control of Hazardous Energies Standard / V5 10032026

The participants shall:

Engage in the above group discussion about the importance of establishing an electrically safe work condition

Engage in the activities and practise:

a. analysing examples of hazardous situations or scenarios in a WTG environment

b. sharing answers about when and why an electrically safe work condition must be established

ELEMENT 3.4 - HOW TO ESTABLISH AN ELECTRICALLY SAFE WORKING CONDITION

Learning objective:

25) The participants can explain the main steps of establishing an electrically safe work condition (Knowledge, intermediate level)

The instructor shall:

Explain and demonstrate examples of how to establish an electrically safe work condition. The steps to establishing a safe work condition are:

a. determine all supplies into the boundary

b. interrupt the load current

c. disconnect the equipment

d. discharge stored energy (if required)

e. visually verify (if possible) that the means of disconnecting is open

f. apply Lockout-Tagout (must be performed by an Authorised Person)

g. test for absence of voltage in all isolations

h. test for absence of voltage in the working area according to the approach boundaries

i.

ground the conductors (if required)

Ask the participants open ended questions about the steps to establishing a safe work condition e.g.:

Global Wind Organisation ©2026 / www.globalwindsafety.org

31 / 110

Made with FlippingBook. PDF to flipbook with ease