Victron Energy Skylla Chargers
Skylla-i Battery Chargers Skylla-i (1+1): two outputs to charge 2 battery banks
Important features: • Synchronised parallel operation • The right amount of charge for a lead-acid battery: variable absorption time • Preventing damage due to excessive gassing: the BatterySafe mode • Less maintenance and ageing when the battery is not in use: the Storage mode • To increase battery life: temperature compensation • Battery voltage sense • Suitable for AC and DC supply (AC-DC and DC- DC operation) • Li-Ion (LiFePO4) ready
The Skylla-i (1+1) features 2 isolated outputs. The second output, limited to approximately 4 A and with a slightly lower output voltage, is intended to top up a starter battery. Skylla-i (3): three full current outputs to charge 3 battery banks The Skylla-i (3) features 3 isolated outputs. All outputs can supply the full rated output Aluminium epoxy powder coated cases with drip shield and stainless steel fixings. Circuit boards are protected with an acrylic coating for maximum corrosion resistance. Flexible Next to a CAN bus (NMEA2000) interface, a rotary switch, DIP switches and potentiometers are available to adapt the charge algorithm to a particular battery and its conditions of use. current. Rugged
Skylla-i
24/80 (1+1)
24/80 (3)
24/100 (1+1)
24/100 (3)
Input Voltage (V AC)
230
Input Voltage Range (V AC) Input Voltage Range (V DC)
185-265 180-350
Maximum AC input current @ 180 VAC
16 A
20 A
Frequency (Hz) Power Factor
45-65
0.98 28.8 27.6 26.4
Charge Voltage ‘absorption’ (V DC)
Charge Voltage ‘float’
Charge voltage ‘storage’ (VDC)
Charge Current House Batt. (A) (2)
80
3 x 80A (max total output: 80A)
100
3 x 100A (max total output: 100A)
Charge Current Starter Batt (A)
4
-
4
-
Charge Characteristic Battery Capacity (Ah) Charge Curve, Li-Ion Temperature Sensor
7 Stage Adaptive
400-800
500-1000
3 stage, with on-off control or CAN bus control
✓ ✓
Can be used as a power supply
Remote on-off port
Yes (can be connected to a Li-Ion BMS)
✓
Forced Cooling Protection (1)
Battery reverse polarity (fuse) Output short circuit Over temperature
Operating Temp. Range Humidity (non-condensing)
-20°C to 60°C (Full output current up to 40°C)
Max 95%
Enclosure
Material & Colour Battery-Connection 230V AC-Connection Protection Category
Aluminium (Blue RAL 5012)
M8 Bolts
Screw-Clamp 10mm² (AWG 7)
IP21
Weight kg (lbs)
7 (16)
Dimensions (mm) H x W x D
405 x 250 x 150
Standards
Safety
EN 60335 - 1, EN 60335 - 2 - 29
Emission Immunity
EN 55014 -1, EN 61000 - 6-3, EN 61000 - 3-2
EN 55014 - 2, EN 61000 - 3 - 3 EN 610006-1, EN 61000-6-2
1) Protection
a. Output short circuit b. Battery reverse polarity detection c. Battery Voltage too high d. Temperature too high 2) Up to 40°C (100°F) ambient
Product Catalogue.
135